Actuator's Features; Installation Instructions - Honeywell V5004TF Installation Instructions Manual

Kombi-qm pressure independent balancing and control valve
Hide thumbs Also See for V5004TF:
Table of Contents

Advertisement

Available languages

Available languages

1

Actuator's features

Proportional control
analogue (voltage and current), PWM, 3 points and ON/
OFF
Position detecting
4-digit display
3 buttons to set parameters
Position control method to set actuator
OS-No.
V5004TF1050
V5004TF1065
V5004TF1080
V5004TF1100
V5004TF1125
V5004TF1150
15000 - 150000
V5004TF1200LF
20000 - 200000
V5004TF1200HF
30000 - 300000
V5004TF1250LF
30000 - 300000
V5004TF1250HF
50000 - 500000
2.
To set the flow on the V5004TF use the digital display
and three buttons on the Smart actuator.
When it is switched on, the Zero Detection function
automatically starts: the display shows "Go 0". Wait
while the actuator is running and the end stroke is
found: finally the display will change to "0".
To enter the settings browser, press the button MODE.
Press UP and DOWN buttons to select the setting.
Press MODE to show different options and browse
using UP and DOWN buttons. Once the option is found,
press MODE to confirm as the selection.
MU0H-2327GE23 R0618
∆ [kPa]
Flow [I/h]
at 30%
flow
2000 - 20000
21
3000 - 30000
26
3000 - 30000
23
5500 - 55000
16
9000 - 90000
21
31
31
32
30
38
GB
2

Installation Instructions

1.
Mount the valve with the arrow in the direction of the
flow
CAUTION!
Mounting it in the wrong direction may damage the
system and the valve itself.
If flow reversal is possible, a non-return valve should be
mounted.
Minimum differential pressure above which the valve begins
to exercise its regulating effect:
Startup Pressure
∆[kPa]
∆[kPa]
at 50%
at 80% flow
flow
25
31
29
30
25
30
20
24
25
31
35
41
35
36
37
38
30
33
49
58
SET1
Input indication selection with internal
control signal
SET2
Control signal selection
SET3
Min. flow rate setting
SET4
Max. flow rate setting
SET5
Setting display mode during operation
SET6
Rotation angle compensation
SET7
Flow rate offset compensation
SET8
Power failure mode
SET9
Flow rate unit selection
SET10
Control curve selection
SET11
Max. voltage control signal
SET12
Min. voltage control signal
SET13
Actuator rotation speed
SET14
Feedback signal selection
3
∆[kPa]
∆[kPa]
at 100%
flow
40
600
30
600
30
600
30
600
35
600
50
600
40
400
40
400
40
400
65
400
Honeywell GmbH