Honeywell V5004TF Installation Instructions Manual page 8

Kombi-qm pressure independent balancing and control valve
Hide thumbs Also See for V5004TF:
Table of Contents

Advertisement

Available languages

Available languages

SET2
SET3
Flow rate on
display
SET4
Flow rate on
display
SET5
SET6*
Value on
display
SET7
Value on
display
SET8
SET9
SET10
SET11*
Value on
display
Honeywell GmbH
Voltage control signal
Voltage control signal
Current control signal
Current control signal
On/Off
3 Point Floating Input
Remote control
PWM 5 Sec
PWM 25 Sec
Internal input
Min. flow rate selection (default:
0)
Max. flow rate selection (default:
depending on model)
Set flow rate in %
Set flow rate in "flow rate"
Current flow rate in %
Current flow rate in "flow rate"
Compensating the max. pulse
% flow rate offset (default: 0)
Valve open at power failure
Valve close at power failure
3
Unit of SI (m
/h)
Unit of GPM (gal/min)
Linear control curve
Equal percentage control curve
Min. voltage control signal
GB
Control with voltage signal
Control with voltage signal
Control with current signal
Control with current signal
24V: open. 0V: close
24 V open if white wire connected (3) 24 V close if green wire
connected (4)
Not available
PWM (0.1 ~ 5 Sec)
PWM (0.1 ~ 25 Sec)
Flow rate set by on board display and buttons.
Push MODE, wait until "Set" is replaced by flow rate
indication (or flow rate %, depending on SET 1), set the flow
rate with UP/DOWN buttons and confirm with MODE.
Set flow values with up/ down buttons and then press
"MODE" to confirm
Set flow values with up/ down buttons and then press
"MODE" to confirm
Select with up/down buttons and then press "MODE" to
confirm
Display option during operation: St allows to see the flow rate
value required by the controller; Fd allows to see the current
flow rate value given by the valve (the progressive change of
flow rate values is displayed during valve stem motion)
Select with up/down buttons and then press "MODE" to
confirm
Select with up/down buttons and then press "MODE" to
confirm
Selection Fail-CLOSE or Fail-OPEN option. Additional
battery needed. Available with VA5004TF0001
Select with up/down buttons and then press "MODE" to
confirm
Select with up/down buttons and then press "MODE" to
confirm
Selection min voltage control value with UP/DOWN buttons
and confirmation with MODE button
8
MU0H-2327GE23 R0618