Features; Optional Features; Specifications - Honeywell 7800 Series Installation Instructions Manual

100 vac relay modules
Hide thumbs Also See for 7800 Series:
Table of Contents

Advertisement

RM7890, RM7895 100 Vac

FEATURES

• Safety features:
— Closed loop logic test .
— Dynamic AMPLI-CHECK™ circuitry .
— Dynamic input check .
— Dynamic safety relay test .
— Dynamic self-check logic .
— Expanded safe-start check .
— Internal hardware status monitoring .
— Tamper resistant timing and logic .
• Access for external electrical voltage checks . Application
flexibility .
• Dependable, long-term operation provided by microcom-
puter technology .
• Five light emitting diodes (LEDs) for sequence informa-
tion .
• Interchangeable type plug-in flame amplifiers .
• Nonvolatile memory retains history files and sequencing
status after loss of power .
• Selectable relight or lockout on loss of flame .

OPTIONAL FEATURES

• Communication interface capability .
• First-out annunciation and system diagnosis are provided
by a two-row by 20-column display located on the option-
al keyboard display module (KDM) .
• Local or remote annunciation operation and fault informa-
tion .
• Remote reset .
• Burner controller data using S7800 Keyboard Display:
— Flame signal strength .
— Hold status .
— Lockout/alarm status .
— Sequence status .
— Sequence time .
— Total cycles of operation .
— Total hours of operation .
• Fault history providing the six most recent faults:
• Cycles of operation at the time of the fault .
• Fault message and code .
• Hours of operation at the time of the fault .
• Sequence status at the time of the fault .
• Sequence time at the time of the fault .
— Diagnostic information:
• Device type .
• Flame amplifier type .
• Flame failure response time . Manufacturing code .
• On/Off status of all digital inputs and outputs .
• Software revision and version of RM7890/ RM7895
and optional Keyboard Display Module .
• Status of configuration jumpers .
32-00216-01

SPECIFICATIONS

Electrical Ratings:
See Table 2.
Voltage and Frequency:
100 Vac (+10/-15%), 50/60 Hz (± 10%).
Power Dissipation: 10W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing Total Connected Load: 15A maximum, type SC or
equivalent.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to 140°F (-40°C to 60°C).
Storage: -60°F to 150°F (-51°C to 66°C).
Humidity: 85% relative humidity continuous, noncondensing.
Vibration: 0.5G environment.
Dimensions:
See Fig. 1 and 2.
Weight:
RM7890, RM7895 with Dust Cover: 1 lb, 13 oz (829 grams)
unpacked.
Approvals:
cULus Underwriters Laboratories Inc. Listed: File No. MP268.
ANSI/UL 60730-2-5 / CSA C22.2 No. 60730-2-5 -
Automatic Electrical Controls for Household and Similar
Use, Part 2-5: Particular Requirements for Automatic
Electrical Burner Control Systems.
FM: Factory Mutual Approved: Report No. 1V9A0.AF.
EAC: TC N RU д-US.Aи3O.B.04013
Exida: IEC/EN 61508:2010 Parts 1-7, SIL 3 capable.
FCC Federal Communications Commission: Part 15, Class B,
Emissions.
Swiss Re (formerly Industrial Risk Insurers): Acceptable.
Mounting:
Q7800A Wiring Subbase for panel mounting.
Q7800B Wiring Subbase for wall or burner mounting.
Required Components:
Plug-in Flame Signal Amplifier (See Table 4).
ST7800A Purge Timer (for RM7895 only).
Accessories:
Keyboard Display Modules (KDM)
S7800A1142 2-Line VFD Keyboard Display Module
S7800A2142 4-line LCD keyboard display module
Communications
Modbus using S7810M1003 Modbus Module
or
configuring the S7800 Keyboard Display.
S7810A1009 Data ControlBus™ Module (if no KDM used).
Miscellaneous
A7800A1002 7800 SERIES Tester
S7820A1007 Remote Reset Module
203541 Data ControlBus Connector, 5-wire
203765 Remote Display Mounting Bracket
221729 Dust Cover, Relay Module