Control Method; Initial Setting - Honeywell V5004TF Installation Instructions Manual

Kombi-qm pressure independent balancing and control valve
Hide thumbs Also See for V5004TF:
Table of Contents

Advertisement

Available languages

Available languages

4

Control Method

1.
Internal control*
2.
Voltage signal
3.
Current signal
* Flow rate can be set by buttons on the actuator and read on the 4 digits display.
5

Initial Setting

Power on display indicates 'Go-0' and automatically adjusts the initial setting to the valve zero point.
Do not press any buttons as this might wrongly adjust the initial setting of the valve zero point; this may cause incorrect flow
control.
The actuator has a built in safety function which can be activated when the zero point cannot be set automatically.
It is activated with the Down button and stops the "Go-0" process.
The zero point may be forced by using the Down button.
How to set: Press the Mode button (about 2 seconds) to switch to the setting mode.
Indication
SET1
MU0H-2327GE23 R0618
Meaning
Input internal control in %
Input internal control in flow rate
GB
4.
ON/OFF
5.
3 points signal
6.
PWM signal
PWM Type 1: 0.1 - 5 s/Step 20ms
PWM Type 2: 0.1 - 25 s/Step 100ms
Select with up/down buttons and then press "MODE" to
confirm