Pl-M2000-Mua (Air Make-Up) - Prolon PL-VC2000 Hardware Manual

Hide thumbs Also See for PL-VC2000:
Table of Contents

Advertisement

PL-M2000-MUA
(Air Make-Up)
INT Port: Incoming RS485
Network Communication
(Modbus)
AO 3 - Variable Frequency Drive
AO 2 - Cooling
AO 1 - Modulating Heat
DO 5 - Alarm
DO 4 - Preheat Permission
DO 3 - Fan
DO 2 - Outside Air Damper
DO 1 - Occupancy (Exhaust)
Bottom Row:
Common for all outputs
NC2000
REV. 6.1.7 / PL-HRDW-I/O-EN
INFO RECEIVED FROM NETWORK
Occupancy (Optional)
Outside temp (Optional)
Bottom Row:
Common for all inputs
CO2 (4-20mA) / Building Pressure (0-5VDC)
Zone Temperature (10K Thermistor)
Outside Temperature (10K Thermistor)
Supply Temperature (10K Thermistor)
Manual Reset
Proof of Fan
Proof Outside Air Damper Open
Proof Exhaust 2 / Manual override
Proof Exhaust 1
NET Port: Incoming RS485 Network
communication (Modbus)
Controller's power source
24 VAC - Class 2
Zone Demand
T1100
Occupancy Override
13