ABB Pluto Series Integration Manual page 24

Table of Contents

Advertisement

For more information about the configuration data see the gateway manual.
dnet_gw> cs
Input Assembly Instance :
0 : Status Only
[100]
1 : Data
Only
[101]
2 : Status/Data
[102]
Select [1] : 1
Output Assembly Instance :
0 : No Data
[112]
1 : To Pluto Data [113]
Select [1] : 1
Expected data from PLUTO 00
Expected data from PLUTO 01
Expected data from PLUTO 02
Expected data from PLUTO 03
Expected data from PLUTO 04
Expected data from PLUTO 05
Expected data from PLUTO 06
Expected data from PLUTO 07
Expected data from PLUTO 08
Expected data from PLUTO 09
Expected data from PLUTO 10
Expected data from PLUTO 11
Expected data from PLUTO 12
Expected data from PLUTO 13
Expected data from PLUTO 14
Expected data from PLUTO 15
Expected data from PLUTO 16
Expected data from PLUTO 17
Expected data from PLUTO 18
Expected data from PLUTO 19
Expected data from PLUTO 20
Expected data from PLUTO 21
Expected data from PLUTO 22
Expected data from PLUTO 23
Expected data from PLUTO 24
Expected data from PLUTO 25
Expected data from PLUTO 26
Expected data from PLUTO 27
Expected data from PLUTO 28
Expected data from PLUTO 29
Expected data from PLUTO 30
Expected data from PLUTO 31
Enable To PLUTO package 0
Enable To PLUTO package 1
Enable To PLUTO package 2
Enable To PLUTO package 3
To PLUTO Timeout [256 ms] : 1000
Save the new configuration [y/n]
dnet_gw>
[Y] ?
YES
[N] ?
YES
[N] ?
YES
[N] ?
YES
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
NO
[N] ?
YES
[N] ?
YES
[Y] ?
YES
[Y] ?
YES
[Y] ?
YES
[Y] ?
YES
YES
24
2TLC172011M0205_B