Operational data
Environmental
conditions
Standards and
directives
Environmental
compatibility
General
Siemens
Building Technologies
Function input:
External temperature sensor, heating/cooling
changeover sensor, operating mode switchover
contact, dewpoint monitor contact, enable electrical
heater contact, alarm contact
Switching differential, adjustable
Heating mode
Cooling mode
Setpoint setting and range
Comfort
Economy
Protection
Multifunctional input X1/X2
Input X1
Input X2
Built-in room temperature sensor
Measuring range
Accuracy at 25 °C
Temperature calibration range
Settings and display resolution
Setpoints
Current temperature value displayed
Storage
Climatic conditions
Transport
Climatic conditions
Operation
Climatic conditions
EU Conformity (CE)
RCM Conformity
Degree of protection of housing
Protective class
Pollution class
The product environmental declarations CE1E3076_1, CE1E3076_2, CE1E3076_3
contain data on environmentally compatible product design and assessments (RoHS
compliance, materials composition, packaging, environmental benefit, disposal).
Connection terminals
Housing front color
Weight
*) The documents can be downloaded from http://siemens.com/bt/download.
1) No condensation is allowed.
RDF300.../RDF340 / RDF400... / RDF600... Flush-mounted Room thermostats
(P30)
(P31)
(P08)
(P11-P12)
(P65-P66)
RDF3..., RDF4...
RDF600...
Selectable
X1: P38
X2: P40
2 K (0.5...6K)
1 K (0.5...6K)
21°C
(5...40 °C)
15°C/30°C (OFF, 5...40 °C)
8°C/OFF
(OFF, 5...40 °C)
Selectable 0...6
3: (P38) operating mode
switchover
2: (P40) heating/cooling
changeover sensor
0...49 °C
< ± 0.5 K
± 3.0 K
0.5 °C
0.5 °C
As per IEC 60721-3-1
Class 1K3
As per IEC 60721-3-2
Class 2K3
As per IEC 60721-3-3
1)
Class 3K5
*)
CE1T3076_1
*)
CE1T3076xx_2
*)
CE1T3076xx_3
*)
CE1T3076_1en_C1
*)
CE1T3076xx_2en_C1
*)
CE1T3076xx_3en_C1
IP 30 to EN 60529
II as per EN 60730-1
Normal
Solid wires or prepared
stranded wires
2
1 x 0.4...1.5 mm
RAL 9003 white
0.220 kg
0.150 kg
CE1N3076en
2018-12-27
*)
11/14