User-Definable Data - ABB Relion 620 Series Protocol Manual

Modbus communication
Hide thumbs Also See for Relion 620 Series:
Table of Contents

Advertisement

Section 3
Vendor-specific implementation
3.4.8
42
Table 22:
16 bit SSR6 register
ClientCmdSEQNo
Cmd State Resp Type
15
14
13
12
11
ClientCmdSEQNo
Counts the client's control operations from 0000...1111, that is 0...15, and then starts
over.
CmdState
00 = No write command has ever been issued by this client
01 = Command in progress
11 = Response Ready
RespType
01 = Unsecured control response
10 = Secured control response
11 = Modbus 03 exception response valid. CMDResultCode is in this case 0. The
reason for the 03 exception is an invalid written value.
Table 23:
CMDResultCode
Code
Meaning
0
OK
201
Device in local mode
202
Control operation reserved by another client
203
Select-timeout or Execute/Cancel without select
204
Control operation internally blocked
205
Control operation timed out
250
Other reason

User-definable data

There can be several reasons for defining UD data. For example, the user may want to
repack a limited amount of important data into sequential addresses and thereafter
only scan this smaller set of data. Especially with serial links, this saves bandwidth and
improves response times.
User-definable register can be used if more advanced rescaling and re-manipulating
of the regular Modbus register is needed. Many of these features are defined for
10
9
8
7
6
1MRS757645 B
CMDResultCode
5
4
3
2
1
620 series
Communication Protocol Manual
0