1MRS757645 B
620 series
Communication Protocol Manual
Setting column
Scaling
Min In
Max In
Min Out
Max Out
Presentation: 32-bit register presentation
Word swap
Presentation: Special retrofit value manipulation
Byte swap
Table continues on next page
Vendor-specific implementation
Alternatives
1)
No scaling
Ratio scaling
Multiplicative scaling
Divisor scaling
Any real value
Any real value
Any real value
Any real value
1)
Unchecked
Checked
1)
Unchecked
Checked
Section 3
Description
No rescaling of the Modbus UDR
value. Scaling arguments are
ignored.
Linear scaling of the source
value between the source range
"Min In"..."Max In" into UDR
value range "Min Out"..."Max
Out". The scaled UDR value
saturates at "Min Out" and "Max
Out" values.
The source value is multiplied
with scaling argument 1 (similar
to argument in Ratio "Min In").
Other scaling arguments are
ignored.
The source value is divided by
the scaling argument 1 (similar to
argument in Ratio "Min In").
Other scaling arguments are
ignored.
Scaling argument 1. Used also
as the scaling factor for
Multiplicative and Divisor
scaling.
Scaling argument 2.
Scaling argument 3.
Scaling argument 4.
32-bit register value expressed
according to "de facto" standard.
Word order High-Low.
32-bit register value word order
changed to Low-High.
16-bit register value expressed
according to Modbus standard.
Byte order High-Low.
16-bit register value byte order
changed to Low-High.