Ascii Character Coding; Ascii String Syntax - ABB Relion 620 Series Protocol Manual

Modbus communication
Hide thumbs Also See for Relion 620 Series:
Table of Contents

Advertisement

Section 3
Vendor-specific implementation
3.4.13.1
3.4.13.2
62
IED model (max. 12 characters)
IED type (max. 6 characters)
IED serial number (max. 12 characters)
IED location information (max. 34 characters)
CPU card SW and HW revision numbers
HMI card SW and HW revision numbers
Slot 0 (X130) card SW and HW revision numbers
Slot 1 (X120) card SW and HW revision numbers
Slot 2 (X115) card SW and HW revision numbers
Slot 3 (X110) card SW and HW revision numbers
Slot 4 (X105) card SW and HW revision numbers
Slot 5 (X100) card SW and HW revision numbers
Slot 6 (X000) card SW and HW revision numbers
The IED does not need to contain cards in all slots nor does a specific
card need to include a CPU. The SW revision information is simply
omitted from the information string.

ASCII character coding

Table 38:
The 8 bit ASCII character coding in the Modbus registers
Modbus register
Register 1 High byte
Register 1 Low byte
Register 2 High byte
:

ASCII string syntax

Syntax
C(model;type;serialNo;location;swRev;hwRev)H(swRev;hwRe
v)0(swRev;hwRev)1(swRev;hwRev)2(swRev;hwRev)3(swRev;hwR
ev)4(swRev;HwRev)
Parenthesis and semicolon ASCII characters are used as delimiters inside the
string.
Section C(...) contains IED information and CPU version information.
Section H(...) contains version information of the LHMI card.
Sections 0(... ) to 4(...) contain version information of the additional HW
cards (slots 0...4).
If an additional card does not include any version information, it is signaled with
a "-" (minus) character in the swRev field. If both swRev and hwRev are
signalled with "-" signs, the card in question does not exist in the IED.
ASCII character
= ASCII character 1
= ASCII character 2
= ASCII character 3
:
Communication Protocol Manual
1MRS757645 B
620 series