User definable data (M10x-P only)

88 Motor control and protection unit | M10x parameter discription
The M10x contains a user definable data area in the memory map. Three data
structures are available for user to define in different applications. Up to 12 bytes
data can be sent out to PROFIBUS master station with three options of 4 bytes, 8
bytes, 12bytes.
The functions for selection are as below:
Type1: 4 bytes in and 2 bytes out
No bytes are mappable. But, in the Configurable area byte1 bit4-7 can be defined
for DIs (DI0~DI12) by user.
Type2: 8 bytes in and 2 bytes out
3 bytes in are mappable by master station.
Data assignable for byte4&5 ( two bytes value only) includes: I
In, U
, U
, U
, Power factor, Earth fault current, Power, Thermistor value,
L1L2
L2L3
L3L1
Running time, Start number, Frequency, Time to TOL trip, Time to TOL reset, Actual
startup time.
Data assignable for byte6: Thermal capacity, Current unbalance
And 12 bits can be defined to DIs(DI0, DI1, DI2, DI3, DI4, DI5, DI6, DI7, DI8, DI9,
DI10, DI11, DI12) by user:
 4 bits come from Configurable area byte1 bit4-7.
 8 bits come from User definable area byte 7 bit0-7
U
, U
, U
, Power factor, Power, Thermistor value and Frequency are
L1L2
L2L3
L3L1
only available for M102 byte4 & byte5.
Type3: 12 bytes in and 2 bytes out
7 bytes in are mappable by master station.
Data assignable for byte4&5 ( two bytes value only) includes: I
In, U
, U
, U
, Power factor, Earth fault current, Power, Thermistor value,
L1L2
L2L3
L3L1
Running time, Start number, Frequency, Time to TOL trip, Time to TOL reset, Actual
startup time.
Data assignable for byte6&7 ( two bytes value only) includes: I
In, U
, U
, U
, Power factor, Earth fault current, Power, Thermistor value,
L1L2
L2L3
L3L1
Running time, Start number, Frequency, Time to TOL trip, Time to TOL reset, Actual
startup time.
/In, I
/In, I
/
L1
L2
L3
/In, I
/In, I
/
L1
L2
L3
/In, I
/In, I
/
L1
L2
L3