Udr Data Configuration; Udr Register Value Manipulation - ABB Relion 620 Series Protocol Manual

Modbus communication
Hide thumbs Also See for Relion 620 Series:
Table of Contents

Advertisement

Section 3
Vendor-specific implementation
3.4.8.6
3.4.8.7
44

UDR data configuration

UDR definitions can be created using the Communication Management tool in
PCM600.

UDR register value manipulation

UDR values are initially copied from the source register. Thereafter the following
manipulations can be applied to the UDR value.
Additional rescaling of the source data value
There are three possibilities for UDR rescaling of the Modbus source register value.
Multiplicative and divisor scaling are similar operations. The defined scale factor can
in both cases be a decimal value. For example, multiplicative scaling by 0.25 is the
same as divisor scaling by 4.
Ratio scaling can be used in the same manner as multiplicative or divisor scaling, but
including an offset. Additionally, it is possible to define new limit ranges for the
resulting register value. Value then saturates (stops) at the defined min. and max.
values. This may be needed for retrofit purposes, in case the relay value must emulate
exactly the same value range as the value from the replaced unit.
For multiplicative and divisor scaling, the register value always saturates at the min.
and max. values for the register type in question. The value does not roll over.
Swapping high and low words within a 32-bit register
32-bit registers do not exist in the Modbus standard. A 32-bit register consists of two
consecutive 16-bit registers that together form the 32-bit value. There is no official
definition for the low-high word order in a 32-bit register. Most vendors, including
this relay, use the order high-low (high word on lower address) as default. In case the
word order would be incorrect, for example in a retrofit case, it is possible to change
it.
Specific retrofit UDR manipulations
Swapping of the byte order within a register word
Redefining the register bit size. Less than 16 bits are used for the value. The used
bits can additionally be left or right justified within the register, that is, they can
appear on either the most significant or least significant side of the register.
1MRS757645 B
620 series
Communication Protocol Manual