Vaillant MultiMatic 700/2 Product Training page 70

Weather compensator
Table of Contents

Advertisement

multiMATIC 700/2
Prompt/setting
Heating curve
Minimum temperature
Maximum temperature
Auto Off mode
Room temp. mod.
Cooling possible
Dew point monitoring
Min. cool. fl. tgt temp.
End OT cooling
Offset dew point
Status ext. heat dem.
Pump status
Mixer status
Notes
10/2015
Select
0.1 - 4.0
15 – 90 °C
15 – 90 °C
Eco, Set-back
None, Temp. mod.,
Thermost.
No, Yes
No, Yes
7 – 24 °C
4 – 25 °C
-10 – 10 K
On, Off
On, Off
Stationary, Closing,
Opening
66
Comment
System-dependent assignment of the outside
temperature to the target flow temperature.
Useful when using radiators
Operating behaviour of the heating circuits
outside the programmed time periods
Factoring in the current room temperature in
order to achieve the target room temperature
Only if the controller is wall-mounted and
zones have been assigned for VRC 700
and/or VR 91
Displayed only if "Cooling possible" =
"Yes" selected
Displayed only if "Cooling possible" =
"Yes", when "Room temp. mod." = "Temp.
mod." and "Zone assignment" = "VRC 700"
or "VR 91" selected
Displayed only with the VR 70 = 1, 5
Displays the status of the pump inside the unit
or the heating circuit pump
Displays the mixer movement
Only for heating circuit 2 and 3, heating
circuit 1 with VR 70 = 3, 5, 12 (mixer circuit)
or VR 71
Training 0020228700_00