CONTACTING VERTIV FOR SUPPORT To contact Vertiv Liebert Services for information or repair service in the United States, call 800-543-2378. Liebert Services offers a complete range of startup services, repair services, preventive maintenance plans and service contracts. For repair or maintenance service outside the 48 contiguous United States, contact Liebert Services, if available in your area.
Read all of the following instructions before attempting to move, lift, or remove packaging from unit, or prepare unit for installation. ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
Page 8
Materials sold hereunder cannot be used in the patient vicinity (e.g., use where UL, cUL or IEC 60601-1 is required). Medical applications such as invasive procedures and electrical life support equipment are subject to additional terms and conditions. ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
• Verify that the UPS room satisfies the environmental conditions stipulated in the equipment specification, paying particular attention to the ambient temperature and air exchange system. ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
However, it is not possible for Vertiv to ensure that foreign bodies will not be introduced during on-site installation, or when the UPS doors and covers are “open” and the electrical terminals are exposed to allow power line connections to be made by the electrical contractor/installer.
If the equipment is to be located on a raised floor, it should be mounted on a pedestal suitably designed to accept the equipment point loading. Refer to the base view to design this pedestal. ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
When bringing the 1+N system on-line for the first time or after removing one unit, Vertiv recommends checking the bypass current mismatch. To check the bypass current mismatch: Place a load on the bypass of each UPS module.
Refer to the drawings provided in 4.0 - Installation Drawings for the positioning of the cabinets as shown in Figure 2. ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
Battery UPS to wire internally Battery Cabinet Cabinets If the cabinets are to be bolted together, the side panels must be removed before beginning. ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
AC and DC cables must be run in conduits according to local codes, national codes and standard best practices. This will prevent creation of excess EMI fields. ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
If a smaller input feed breaker is used, the input current limit can be adjusted; see your Vertiv representative for more information. The input current limit should not be set less than 105% of the current needed to support the inverter at full load for normal operation.
All operations described in this section must be performed by properly trained and qualified electricians or technical personnel. If any difficulties are encountered, contact Vertiv. See the back page of this manual for contact information.
, Liebert SiteScan Web and Liebert ® Nform The Liebert IS-UNITY-DP supports up to two third-party protocols along with HTTP/S (Web), Vertiv Protocol, SMTP and SMS. Third-party protocols available on the Liebert IS-UNITY-DP card are: • BACnet IP—BACnet over Internet Protocol •...
This slot is the reserved interface for LIFE Services modem card. This card provides an independent external modem interface for communication with LIFE Services service station. Ask your local Vertiv representative for more details on LIFE Services and its benefits for your UPS system.
Use 16-22AWG cable. All input contacts can be programmed using service software. WARNING To drive the inputs, use no-voltage contacts. Do not use voltages supplied by external power supply. ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
See Figures 20 and 21 for recommended wiring layout. Eco Mode must be set up by an Vertiv Liebert Services customer engineer. Once set up, Eco Mode becomes the default operating mode: It shifts the load to bypass if utility power is within specified limits and to double-conversion (on-line) mode if utility power falls outside the limits.
Conduit-based grounding systems tend to degrade over time. Therefore, using conduit as a grounding conductor for UPS applications may degrade UPS performance and cause improper UPS operation. ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
Risk of improper installation. Can cause equipment damage. Failure to set the ground fault interrupters properly could cause loss of power to the critical load. Figure 3 Grounding diagram—Three-wire single-module systems Source BPSS ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
Center-tapped or grounded battery systems are not possible with battery cabinet systems. Whether the battery system is open-rack or cabinet, the metal rack parts or cabinet must be grounded to the UPS module ground bus. ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
UPS so that interlocks will function properly and for the HMI to indicate the bypassed status of the module. Vertiv recommends using magnetic or thermomagnetic breakers. If molded case switches will be used, Vertiv recommends installing breakers without electronic trip units or to set the trip units as follows: •...
REPO connections 1+N system UPS 1 UPS 2 REPO Relay Contacts Switchgear or Panelboard Cabinet UPS N All auxilliary contacts from the REPO must be isolated. ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
300kVA/KW (from 225 or 250kVA/kW) or 600kVA KW(400 and 500kVA/kW). If this upgrade is planned, breakers and conductors should be sized for the final capacity. ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
This module is available to support up six or up to 11 UPS modules, and is generally configured to synchronize all modules to a reference bus (e.g., bypass line). See the manual for this module for more details. ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
10. See technical data drawing for shipping weights. U38-3C-2001 11. The height is to the top of the frame; fans rise 1.5" (38.1mm) above the frame. Rev. 4 ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
Run the control wires to through the conduit plate provided. If the unit is not on a raised floor, then insert a rubber grommet into the conduit plate hole (at the bottom of the entry location for the low-voltage control wiring). ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
Pad to Outside Door Panel DETAIL A Unit bottom is structurally adequate for forklift handling front or rear only. Rail 1.7" (42mm) RIGHT ISOMETRIC VIEW WITHOUT KICKPLATE ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
11. See technical data drawing for shipping weights. U38-6C-2001 11. The height is to the top of the frame; fans rise Rev. 5 1.5" (38.mm) above the frame. ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
1.7" FOOTPRINT SPACING (42mm) Top View U38-6L-1000 RIGHT ISOMETRIC VIEW Unit bottom is structurally adequate Rev. 0 WITHOUT KICKPLATE for forklift handling front or rear only ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
Front Door Opening (for serviceability) More than 90° Degree of Protection for UPS Enclosure IP 20 (with and without front door open) Minimum Clearance, Top, in (mm) 24 (610) ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
Rating up to 4921ft. (1500m) up to 6562ft. (2000m) Altitude up to 9842ft. (3000m) Table 9 Current ratings—rectifier input UPS Rating Voltage Nominal Maximum Current Current ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
14.5 (—) 14.5 (—) The inverter overload is based on 104°F (40°C) ambient. At lower ambient temperatures, the overload timers automatically adjust to longer run times. ™ ® ™ Vertiv | Liebert 225-600kVA Installation Manual | Rev. 8 | 07/2017...
(5) 2.5C, 2-600kcmil; 250kcmil Recommended cable sizes are 167°F (75°C) (THW) wire at 86°F (30°C) ambient. For continuous operations not at 86°F (30°C), Vertiv recommend that the site planner choose the appropriate cable type based on the particular installation requirements.
Page 51
TECHNICAL SUPPORT / SERVICE Web Site www.vertivco.com Monitoring liebert.monitoring@vertivco.com 800-222-5877 Outside North America: +00800 1155 4499 Three-Phase UPS & Power Systems 800-543-2378 Outside North America: 614-841-6598 LOCATIONS United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111...