Thermostatic Expansion Valve (Txv) - Carrier 50TC*17 Series Service And Maintenance Instructions

Nominal 15 to 27.5 tons, with puron r-410a refrigerant
Table of Contents

Advertisement

THERMOSTATIC EXPANSION
VALVE (TXV)
All two−stage 50TC units with Humidi−MizerR have a
factory installed nonadjustable thermostatic expansion
valve (TXV). The TXV will be a bi-flow, bleed port
expansion valve with an external equalizer. TXVs are
specifically designed to operate with PuronR or R-22
refrigerant, use only factory authorized TXVs. See Fig.
20.
TXV Operation
The TXV is a metering device that is used in air
conditioning and heat pump systems to adjust to changing
load conditions by maintaining a preset superheat
temperature at the outlet of the evaporator coil.
The volume of refrigerant metered through the valve seat
is dependent upon the following:
1. Superheat temperature is sensed by the cap tube sens-
ing bulb on suction the tube at the outlet of evapora-
tor coil. This temperature is converted into pressure
by refrigerant in the bulb pushing downward on the
diaphragm which opens the valve using the push rods.
2. The suction pressure at the outlet of the evaporator
coil is transferred through the external equalizer tube
to the underside of the diaphragm.
3. The needle valve on the pin carrier is spring loaded,
exerting pressure on the underside of the diaphragm.
Therefore, the bulb pressure equals the evaporator
pressure (at the outlet of the coil) plus the spring pres-
sure. If the evaporator load increases, the temperature
increases at the bulb, which increases the pressure on
the topside of the diaphragm, pushing the carrier
away from the seat, opening the valve and increasing
the flow of refrigerant. The increased refrigerant flow
causes increased leaving evaporator pressure which
is transferred through the equalizer tube to the under-
side of the diaphragm. This causes the pin carrier
spring pressure to close the TXV valve. The refriger-
ant flow is effectively stabilized to the load demand
with a negligible change in superheat.
Replacing TXV
CAUTION
PERSONAL INJURY HAZARD
Failure to follow this CAUTION can result in injury
to personnel and damage to components.
Always wear approved safety glasses, work gloves,
and
other
recommended
Equipment (PPE) when working with refrigerants.
1. Disconnect all AC power to the unit. Use approved
lockout/tagout procedures.
2. Using the gauge set approved for use with Puron (R−
410A) refrigerant, recover all refrigerant from the
system.
Personal
Protective
17
3. Remove the TXV support clamp.
4. Disconnect the liquid line at the TXV inlet.
5. Remove the liquid line connection at the TXV inlet.
6. Remove the equalizer tube from the suction line of
the coil. Use a tubing cutter to cut the brazed equaliz-
er line approximately 2 inches (50 mm) above the
suction tube.
7. Remove the bulb from the vapor tube above the evap-
orator coil header outlet.
8. Install the new TXV; avoid damage to the tubing or
the valve when attaching the TXV to the distributor.
Protect the TXV against over−temperature conditions
by using wet rags and directing the torch flame tip
away from the TXV body. Connect the liquid line to
the TXV inlet by repeating the above process.
9. Attach the equalizer tube to the suction line. If the
replacement TXV has a flare nut on its equalizer line,
use a tubing cutter to remove the mechanical flare nut
from the equalizer. Then use a coupling to braze the
equalizer line to the stub (previous equalizer line) in
the suction line.
10. Attach the TXV bulb in the same location as the orig-
inal (in the sensing bulb indent), wrap the bulb in pro-
tective insulation and secure using the supplied bulb
clamp. See Figs. 19 and 21.
TXV SENSOR BULB
SENSOR BULB
INDENT
DIRECTION OF
REFRIGERANT FLOW
SENSOR BULB
INSULATION
Fig. 19 − TXV Sensor Valve Insulation
11. Route the equalizer tube through the suction connec-
tion opening (large hole) in the fitting panel and in-
stall the fitting panel in place.
12. Sweat the inlet of the TXV marked "IN" to the liquid
line. Avoid excessive heat which could damage the
valve.
13. Check for leaks.
14. Evacuate the system completely and then recharge.
15. Remove the lockout/tagout on the main power switch
and restore power to the unit.
16. Complete the charging procedure.
Refrigerant System Pressure Access Ports
There are two access ports in the system: on the suction
tube near the compressor, and on the discharge tube near
the compressor. These are brass fittings with black plastic
caps. The hose connection fittings are standard 1/4 SAE
male flare couplings. See Fig. 15.
The brass fittings are two-piece High Flow valves, with a
receptacle base brazed to the tubing and an integral
spring-closed check valve core screwed into the base. This
check valve is permanently assembled into this core body
CAPILLARY TUBE
EQUALIZER TUBE
TO TXV
FROM TXV VALVE
15.9 mm
(REF)
C10372

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents