Service

6.1 Transmitter check
list
YES
Power on transmitter,
display light on
NO
Check cables/connections
YES
Check connection board
Check pins in transmitter
multiplug - OK
NO
Correct fault
6.
Service
Often problems with unstable/wrong measurements occur due to insufficient/wrong earthing or
potential equalization. Please check this connection. If OK, the SITRANS F M MAGFLO
mitter can be checked as described in the handbook.
When checking SITRANS F M MAGFLO
check the transmitter is to replace it with another MAG 6000 I electronic insert with a similar power
supply.
If no spare electronic insert is available - then check transmitter according to check table.
YES
Output
Display defect
readings OK
Change display
NO
transmitter
defective
SFIDK.PS.026.E5.02
®
installations for malfunction the easiest method to
YES
Error triangles flashing
NO
YES
Output and display
readings OK ?
NO
Check cables/connections
YES
Check connection board
Check pins in transmitter
multiplug - OK
NO
Correct fault
®
trans-
Check error table
Transmitter OK -
Check settings/application
Check installation/sensor/
earthing connection etc.
39