Siemens Sitrans F M Magflo Operating Manual page 38

Electromagnetic flowmeters
Hide thumbs Also See for Sitrans F M Magflo:
Table of Contents

Advertisement

® ® ® ® ®
SITRANS F M MAGFLO
5.6.3
List of error numbers
Note
Some error codes might
never appear in the
MAG 6000 I
38
5.
Commissioning
Error
Error text
No.
Remedy text
1
I1 - Power on
OK
2
I2 - Add-on module
Applied
I3 - Add-on module
3
Install
4
I4 - Param. corrected
OK
20
W20 - Totalizer 1
Reset manually
20
W20 - Totalizer 2
Reset manually
21
W21 - Pulse overflow
Adj. pulse settings
22
W22 - Batch timeout
Check installation
23
W23 - Batch overrun
Check installation
24
W24 - Batch neg. flow
Check flow direction
30
W30 - Overflow
Adj. Q
max.
31
W31 - Empty pipe
®
P40 - SENSORPROM
40
Insert/change
41
P41 - Parameter range
Switch off and on
42
P42 - Current output
Check cables
43
P43 - Internal error
Switch off and on
®
44
P44 - CT SENSORPROM
F60 - CAN comm. error
60
Transmitter/AOM
®
61
F61 - SENSORPROM
error
Replace
®
62
F62 - SENSORPROM
ID
Replace
®
F63 - SENSORPROM
63
Replace
70
F70 - Coil current
Check cables
71
F71 - Internal error
Replace transmitter
SFIDK.PS.026.E5.02
#Comment
Power on has happened
A new module has been applied to the system
An add-on module is defect or has been removed.
This can be an internal add-on module
A less vital parameter in the transmitter has been re-
placed by its default value
During initialisation the check of the saved totalizer
value has failed. It is not possible to rely on the
saved totalizer value anymore. The totalizer value
must be reset manually in order to rely on future
readings
During initialisation the check of the saved totalizer
value has failed. It is not possible to rely on the
saved totalizer value anymore. The totalizer value
must be reset manually in order to rely on future
readings
Actual flow is too big compared with pulse width and
volume/pulse
Duration of batching has exceeded a predefined
max. time
Batch volume has exceeded a predefined maximum
overrun volume
Negative flow direction during batch
Flow is above Q
settings
max.
Pipe is empty
®
SENSORPROM
unit not installed
A parameter is out of range. The parameter could not
be replaced by its default value. The error will dis-
appear at the next power-on
Current loop is disconnected or the loop resistance
is too big
Too many errors occured at the same time
Some errors are not detected correctly
®
SENSORPROM
unit has been used as CT version
CAN bus communication error. An add-on module, the
display module or the transmitter is defect
It is not possible to rely on the data in SENSOR-
®
PROM
unit anymore
®
The SENSORPROM
unit ID does not comply with the
product ID.
®
The SENSORPROM
unit is from another type of
®
®
product MASSFLO
, SONOFLO
etc.
It is not possible to read from the SENSORPROM
unit anymore.
Coil excitation has failed
Internal convertion error in ASIC
Outputs
Input
status
status
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Reduced
pulse width
Active
Batch out-
put on zero
Active
Batch out-
put on zero
Active
Active
Active
Max. 120 %
Active
Zero
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Active
Zero
Inactive
Active
Active
Zero
Inactive
®
Active
Active
Active
Active
Active
Active