Carrier VVT 33ZCVVTZC-01 Installation, Start-Up And Configuration Instructions page 31

3v control system. zone controller pressure dependent control
Hide thumbs Also See for VVT 33ZCVVTZC-01:
Table of Contents

Advertisement

→ Table 6 — Terminal Service Configuration Table
DESCRIPTION
COOLING
Terminal Type
1 = Single Duct
2 = Parallel Fan
3 = Series Fan
Primary Inlet Size
Inlet Diameter (Inches)
Inlet Area (Sq. In.)
Damper PID
Proportional Gain
Integral Gain
Derivative Gain
Starting Value
CW Rotation
HEATING
Heat Type
0 = None
2 = Two Position
3 = Staged Electric
4 = Modulating/CV
5 = Combination
Heating PID
Proportional
Integral Gain
Derivative Gain
Starting Value
Ducted Heat
Maximum Temperature
# Electric Heat Stages
Heat On Delay
Fan Off Delay
2-Pos Heat Logic
System Call for Heat?
Supp. Heat Lockout Temp.
System Pilot Averaging
0 = System Pilot only
1 = with one T55
2 = with four T55s
3 = with nine T55s
SPT Sensor Trim
SAT Sensor Trim
Local SAT Installed
Remote Contact Config
VALUE
UNITS
1
6.0
0.0
10.0
2.5
4.0
40.0
%
Close
0
10.0
0.5
0.0
80.0
dF
Yes
110
dF
3
2
min
2
min
Normal
Yes
140.0
dF
0
0.0
^F
0.0
^F
Yes
Close
31
NAME
TERMTYPE
RNDSZ
SQA
KP
KI
KD
STARTVAL
DMPDIR
HEATTYPE
KP
KI
KD
STARTVAL
DUCTHEAT
MAXTEMP
STAGES
HONDEL
FNOFFD
HEATYPE
HEATCALL
SHL_TEMP
SENS_AVG
SPTTRIM
SATTRIM
LOC_SAT
RMTCFG
1104