Technical specifications
6.7 Technical specifications for terminal modules
Table 6-6
Terminal modules TPF (use), 3-wire initiators with LED, incl. fuse in the signal path
6ES7924-0CL20-0Bx0
Type of supply voltage
Operating voltage
Max. permissible continuous current per signal
Max. permissible total current
(power supply)
Fuse
Factory fittings
General data
Connection to SIMATIC fitted for
Operating temperature
Mounting position
Clearances and creepage distances
Dimensions (W x H x D) in mm
For 3-wire initiators with fuse
6ES7924-0CL20-0Bx0
Table 6-7
Terminal modules TPS (witch), 3-wire initiators with LED, incl. switch in the signal path
6ES7924-0CH20-0Bx0
Type of supply voltage
Operating voltage
Max. permissible continuous current per signal
Max. permissible total current
(power supply)
Switch
Type
Activation during operation
General data
Connection to SIMATIC fitted for
Operating temperature
Mounting position
66
Technical specifications for terminal module TPF with LED
Technical specifications for terminal module TPS with LED
DC
max. 24 V
1 A (limited with 0.6 A microfuse)
4 A / byte
5 mm x 20 mm microfuse
0.6 A / 250 V quick-response
16-pin IDC connector with fitted strain relief
0 to + 60° C
Any
IEC 60664-1, IEC61131-2,
CSA C22.2 No 142 UL 508, VDE 0160,0
overvoltage category II,
pollution degree 2
Approx. 57 x 76 x 60
DC
max. 24 V
1 A
4 A / byte
DIP slide switch
Activation during operation permitted,
Max. switching capacity 10VA,
ON = "top" position, set to "ON"
16-pin IDC connector with fitted strain relief
0 to + 60° C
Any