Download Print this page
ComAp InteliNano NT MRS Fast User's Manual
ComAp InteliNano NT MRS Fast User's Manual

ComAp InteliNano NT MRS Fast User's Manual

Hide thumbs Also See for InteliNano NT MRS:

Advertisement

Quick Links

ComAp,a.s.
Kundratka 2359/17
180 00, Praha 8
Czech Republic
InteliNano NT
Typical wiring diagram
DIESEL / GASOLINE ENGINE
GENERATOR
G
ECU
D+
PC
Accessing the setup mode
Ensure the engine is stopped and the controller is in Manual mode (green LED above button
If you have not configured the custom initialization (init) screen then press and hold
If you have already created your own init screen then press and hold
button. Then press
to switch LCD to default init screen, and then press
To move up and down in the setup menu use
Engine parameters and protections
Outputs and inputs
Output
Output source
code
O00
Not Used
O01
Starter
O02
Fuel Solenoid
O03
Stop Solenoid
O04
Alarm
O07
Ready To Load
O08
Prestart
O09
ECU Power Relay
O10
Choke
O11
Glow Plugs
Normally Open Contact – output
Normally Closed Contact – output
User curves
I21
VDO Level %
VDO 5 Bar
Datcon Level %
VDO 10 Bar
Datcon 5 Bar
Datcon 7 Bar
Datcon 10 Bar
Not selected
Not selected
InteliNano-NT MRS, SW version 1.5, ©ComAp – September 2013
InteliNano-NT-MRS-1.5-Fast User Guide.pdf
MRS
LOAD
L1
L2
L3
N
Stop
button and then briefly press
.
Auto
Start
and
buttons. Press
button to select or
Basic settings
Generator protections
Output settings
Type
Terminal assignment
binary T04, T05, T06, T07
binary T04
binary T04, T05, T06, T07
binary T04, T05, T06, T07
binary T04, T05, T06, T07
binary T04, T05, T06, T07
binary T04, T05, T06, T07
binary T04, T05, T06, T07
binary T04, T05, T06, T07
binary T04, T05, T06, T07
Normally Open Contact - input
button
Normally Closed Contact – input
button
I23
I25
VDO 40-120 °C
VDO 50-150 °C
Datcon High °C
Datcon Low °C
Not selected
Case dimensions: 118mm x108mm x 40mm
Panel Cutout: 96mm x 96mm
GENERATOR VOLTAGE
MEASUREMENT
T16 = Neutral
T17 = Phase 1
T18 = Phase 2
T19 = Phase 3
USB interface
INTPUT TERMINALS
T10 = COM for analog inputs
T11 = binary input
T12 = binary input
T13 = binary/analog input – Low Fuel Level
T14 = binary/analog input – Coolan Temperature
T15 = binary/analog input – Oil Pressure
W
!
ARNING
If D+ is not used, connect this terminal to battery positive!
Auto
is turned off).
Stop
button, then briefly press
button and then
, the custom init screen will appear, keep holding the
Stop
button for exit.
Input
Input source
code
I00
Not Used
I01
Emergency Stop
I02
Remote Start/Stop
I03
Remote Start And Load
I04
Access Lock
I07
GCB Feedback
I10
External Warning 1
I11
External Warning 2
I12
External Warning 3
I13
External Shutdown 1
I14
External Shutdown 2
I15
External Shutdown 3
I20
Low Fuel Level
I21
Fuel Level Analog
I22
Low Oil Pressure
I23
Oil Pressure Analog
I24
High Coolant Temperature
I25
Coolant Temperature Analog
I29
Fuel Level SD
1
Fast User Guide
Dimensions
CAN INTERFACE
POWER SUPPLY, D+
T01 = BATT -
T02 = D+
T03 = BATT +
OUTPUT TERMINALS
T04 = binary output – Starter (6A)
T05 = binary output - Fuel Solenoid (6A)
T06 = binary output (500 mA)
T07 = binary input/output (500 mA)
.
Auto
Stop
Input settings
ECU setting
Info
Type
Terminal assignment
binary T07, T11, T12, T13, T14, T15
binary T07, T11, T12, T13, T14, T15
binary T11
binary T11
binary T07, T11, T12, T13, T14, T15
binary T07, T11, T12, T13, T14, T15
binary T07, T11, T12, T13, T14, T15
binary T07, T11, T12, T13, T14, T15
binary T07, T11, T12, T13, T14, T15
binary T07, T11, T12, T13,T14, T15
binary T07, T11, T12, T13, T14, T15
binary T07, T11, T12, T13, T14, T15
binary T07, T11, T12, T13, T14, T15
analog T13, T14, T15
binary T07, T11, T12, T13, T14, T15
analog T13, T14, T15
binary T07, T11, T12, T13, T14, T15
analog T13, T14, T15
Binary T07, T11, T12, T13, T14, T15
L
COM
H

Advertisement

loading

Summary of Contents for ComAp InteliNano NT MRS

  • Page 1 Binary T07, T11, T12, T13, T14, T15 Datcon High °C Datcon 5 Bar Datcon Low °C Datcon 7 Bar Datcon 10 Bar Not selected Not selected Not selected InteliNano-NT MRS, SW version 1.5, ©ComAp – September 2013 InteliNano-NT-MRS-1.5-Fast User Guide.pdf...
  • Page 2 Max. measured voltage 340 V Ph-N Voltage accuracy Charging alternator preexcitation circuit 40 – 70 Hz Frequency range Excitation current 100 mA Frequency accuracy Charging fail threshold 80 % InteliNano-NT MRS, SW version 1.5, ©ComAp – September 2013 InteliNano-NT-MRS-1.5-Fast User Guide.pdf...