Download Print this page

Ametek GEMCO 1746R Series Installation & Programming Manual page 19

Plc resolver interface module; for allen-bradley slc 500 i/o chassis

Advertisement

Spec Tech Industrial Electric
Chapter 4: Application Examples
On the first scan, the start 1746R configuration flag is set. When this flag is set, the configuration command is
copied into the output image table with the programming bit set. This will continue until the command has been
acknowledged in the input image table.
CLEAR STATE FLAGS AND SET UP FOR INITIALIZATION
First Pass
S2:1
0000
15
COPY COMMAND TO CONFIGURE THE 1746R CARD
Config Bit Set
Ack Bit Cleared
N10:0
0001
0
OTHER
When the 1746R configuration command is complete, the program will copy the position scaling command for
resolver 1 into the output image table with the programming bit set. This command will configure resolver 1 for
a total scale factor of 1000 and turn count of 10. This will configure the resolver for 100 counts per turn. This
continues until the command has been acknowledged.
WHEN COPY OF THE 1746R CONFIGURATION COMMAND IS COMPLETE, SET THE STATE FLAG TO
CONFIGURE RESOLVER 1
Config Bit Set
Ack Bit Set
N10:0
0002
0
OTHER
COPY THE COMMAND TO CONFIGURE RESOLVER 1 WITH SCALE FACTOR AND TURNS COUNTING
INFORMATION
Res 1 Config Bit Set
N10:0
0003
1
Spec Tech Industrial Electric
www.spectechind.com
I:1
15
Program Bit Set
O:1
I:1
15
15
OTHER
Ack Bit Cleared
I:1
15
OTHER
Installation & Programming Manual
www.spectechind.com
888-773-2832
MOV
Move
Source
1
1<
Dest
N10:0
0 <
Clear Program Bit
O:1
( U )
15
OTHER
COP
Copy File
Source
#N7:0
Dest
#O:1.0
Length
8
MOV
Move
Source
2
2 <
Dest
N10:0
0 <
Clear Program Bit
O:1
( U )
15
OTHER
COP
Copy File
Source
#N7:10
Dest
#O:1.0
Length
8
16
888-773-2832