Table 7- 2
Test voltage for 6EP1437-3BA10
Type test
Production test
Field test
Remark:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: <100 mA
SITOP PSU8200 3ph
Manual, 11.2014, C98130-A7638-A1-2-7629
Test time
Prim ↔ sec (A)
60 s
4200 VDC
60 s
3000 VAC
1 s
2200 VDC
1 s
1500 VAC
1 s
2200 VDC
1 s
1500 VAC
Safety, approvals, EMC
Prim ↔ PE (B)
Sec ↔ PE (C)
2200 VDC
700 VDC
1500 VAC
500 VAC
2200 VDC
500 VDC
1500 VAC
350 VAC
2200 VDC
500 VDC
1500 VAC
350 VAC
7.2 Test voltage
41