Overview; The Performancealert™ Gateway System; The Performancealert™ Gateway Board; The Performancealert™ Diagnostic Module - Emerson Copeland PerformanceAlert Installation And Operation Manual

Gateway system
Table of Contents

Advertisement

1

Overview

The PerformanceAlert™ Gateway is designed to allow
the Emerson Climate Technologies Retails Solutions fam-
ily of site controllers (E2, Einstein, and REFLECS) to in-
terface directly with up to 14 Copeland
PerformanceAlert™ Diagnostic Modules.
The Gateway uses two network ports: one, a MODBUS
port used to connect the Gateway with the Perfor-
manceAlert™ modules, and the second an I/O network port
that connects the Gateway to the I/O network of an E2 or
Einstein control system (or COM A/D of a REFLECS net-
work).
The Gateway mimics the behavior of a MultiFlex 16 in-
put board, passing along data from the PerformanceAlert™
modules about compressor behavior to the site controller in
the form of virtual board/point addresses. The Gateway's
board/point addresses may be used by the site controller for
I/O control, logging, and alarming.
1.1.
The PerformanceAlert™
Gateway System
Figure 1-1 - Typical Layout of PerformanceAlert™ Modules and
Gateway Board
A typical layout of a CPC-controlled Perfor-
manceAlert™ network configuration is shown in Figure 1-
1. Each compressor in each rack is equipped with one Per-
formanceAlert™ Diagnostic Module. All modules are
wired together in a single MODBUS daisy-chain and con-
nected to the PerformanceAlert™ Gateway board. The
Gateway Board is also connected to the E2 via the I/O net-
work, where it mimics the behavior of a MultiFlex input
board (16AI) and sends values from the modules to the E2
as virtual board/point addresses.
The PerformanceAlert™ Gateway System
1.2.
®
Figure 1-2 - Gateway Board
you to connect up to fourteen (14) PerformanceAlert™ Di-
agnostic Modules. On the I/O network, the Gateway board
mimics the behavior of one or more 16AI boards, which
use virtual 16AI board/point addresses to pass along infor-
mation from the modules to the E2.
ing in one of two different modes: a Condensed Mode,
which maps a single 16AI point to the alarm status of each
PerformanceAlert™ module, and an Expanded Mode,
which maps sixteen 16AI points for each module, includ-
ing alarm status for all alarm types, current transducer val-
ues, and discharge line temperature.
mimics the equivalent of one 16AI board. In Expanded
Mode, the PerformanceAlert™ Gateway mimics the equiv-
alent of up to fourteen 16AI boards.
1.3.
ule is a breakthrough innovation for troubleshooting refrig-
eration system faults. The module can be installed in the
electrical box of the condensing unit near the compressor
contactor or in the electrical panel of a refrigeration rack
system. By monitoring and analyzing data from the Cope-
land
the cause of electrical and system related issues.
The PerformanceAlert™
Gateway Board
9
8
LEGEND
1
Hand-Held Terminal Jack
2
RS485 I/O Network
3
RS485 Receiver Bus Net
4
10
I/O Net Term Jumpers
5
11
Receiver Bus Term Jumpers
6
General Status LED
The PerformanceAlert™ Gateway (Figure 1-2) allows
The PerformanceAlert™ Gateway is capable of operat-
In Condensed Mode, the PerformanceAlert™ Gateway
The PerformanceAlert™
Diagnostic Module
®
The Copeland
PerformanceAlert™ Diagnostic Mod-
®
brand compressors, the module can accurately detect
5
4
11
3
10
2
1
7
6
7
Alarm Status LED
8
Dip Switch
9
Power Connector
I/O Net Status LED
Receiver Bus Status LED
26502044
Overview • 1