P02: Differential of St2
P02 defines the hysteresis of St2 (that is the width of the regulation zone). It is a relative value which can have the same value as St2 or
can be set on its right or on its left.
Access:
Keypad: :
Remote control:
Modes:
Other parameters:
Operating range:
Default:
Note: the type of set-point depends on C03.
C03: Type of set-point
C03 indicates if the set-point corresponds to the min., max. or average value of the analogue output.
Access:
Keypad:
Remote control:
Modes:
Other parameters
Operating range:
Ü
C03=0
Ü
C03=1
Ü
C03=2
Default:
8.2

Parameters concerning the analogue output

C04: Minimum output value
C04 defines the min. value of the 0
Access:
Keypad:
Remote control
Other parameters:
Operating range:
Default:
C05: Maximum output value
C05 defines the maximum value of the analogue output in %.
Access:
Keypad:
Remote control:
Other parameters:
Operating range:
Default:
C06: Soft-start
C06 defines the max. variation speed necessary to change the value of the analogue output, that is the time interval necessary to pass
from 0 to 100% and vice-versa.
Access:
Keypad:
Remote control:
Other parameters:
Operating range:
Default:
Note: setting too long time-intervals may cause hunting problems.
FCM electronic regulator
Ü
if C50=1 or 3
Ü
if C50=0, 2 or 4
Ü
if C50=0, 1 or 4
Ü
if C50= 2 or 3
in modes based on the presence of two different set-points, C00=5, 6, 7 and 8
does not depend on other parameters.
from 0.0 to 100 (180°F).
P02 = 2.0 (3.6°F).
Ü
if C50=1, 3 or 4
Ü
if C50=0 or 2
Ü
if C50=4
in all modes except C00=0 and 1 ("SLAVE DIRECT" and "SLAVE REVERSE" )
does not depend on other parameters.
from 0 to 2
set-point corresponds to the min. output value
set-point corresponds to the average output value
set-point corresponds to the max. output value
Ü
C03=0
set-point corresponding to the min. output value.
÷
10 V analogue output, expressed in %.
Ü
if C50=1, 3 or 4
Ü
if C50=0 or 2
Ü
if C50=4
does not depend on other parameters.
from 0% to C05 (max. output value).
C04 = 0%.
Ü
if C50=1, 3 or 4
Ü
if C50=0 or 2
Ü
if C50=4
does not depend on other parameters.
from C04 (min. output value) to 100%.
C05 = 100% .
Ü
if C50=1, 3 or4
Ü
if C50=0 or 2
Ü
if C50=4
does not depend on other parameters.
from 0 to 120 seconds.
C06 = 2 s. .
press
for 5";
the parameter can only be displayed.
direct access pressing "ENABLE" and, after that, the dedicated buttons;
the parameter can only be displayed.
press
+
for 5" and password 77;
the parameter can only be displayed.
press "ENABLE" and
and
+
for 5" and password 77
the parameter can only be displayed.
direct access pressing "ENABLE" and, after that, the dedicated buttons.
+
for 5" and password 77;
the parameter can only be displayed.
direct access pressing "ENABLE" and, after that, the dedicated buttons
+
for 5" and password 77;
the parameter can only be displayed.
press "ENABLE" and
and
16
;
;
Cod. +302235300 - Rel. 2.0 del 30/11/98