Maximum Fuse Rating On Alternating Current Side - Fronius Symo Installation Instructions Manual

Grid-connected inverter
Hide thumbs Also See for Symo:
Table of Contents

Advertisement

Maximum fuse
rating on alternat-
AC ~
ing current side
Inverter
Fronius Symo 3.0-3-S / -M
Fronius Symo 3.7-3-S / -M
Fronius Symo 4.5-3-S / -M
Fronius Symo 5.0-3-M
Fronius Symo 6.0-3-M
Fronius Symo 7.0-3-M
Fronius Symo 8.2-3-M
If overlength AC or DC cables are to be laid
in loops in the connection area, attach the
cables with cable ties to the eyelets provi-
ded on the top and bottom of the connecti-
on block.
max. C 25 A
Phases
AC power
3
3000 W
3
3700 W
3
4500 W
3
5000 W
3
6000 W
3
7000 W
3
8200 W
Maximum
Recommend-
fuse rating
ed fuse rating
C 25 A
C 10 A
C 25 A
C 13 A
C 25 A
C 16 A
C 25 A
C 16 A
C 25 A
C 16 A
C 25 A
C 20 A
C 25 A
C 25 A