Honeywell NXL Series Applications Manual page 60

Hvac drives
Hide thumbs Also See for NXL Series:
Table of Contents

Advertisement

Page 60 (68)
PFC with interlocks and autochange between 2 pumps
Situation: 1 controlled drive and 1 auxiliary drive.
Parameter settings: 2.10.1= 1
Interlock feedback signals used, autochange between pumps used.
Parameter settings: 2.10.4=4
The interlock feedback signals come from the digital input DIN2 (par. 2.1.15.17) and
digital input DIN3, (par. 2.1.15.18).
The control of pump 1 (par.2.3.1=17) is enabled through Interlock 1 (DIN2, P2.1.15.17),
the control of pump 2 (par.2.3.2=18) through Interlock 2 (par. 2.1.15.18=13)
Reference
potentiometer
2-wire
transmitter
Actual
value
I
(0)4...20 mA
4
Description of parameters
Terminal
1
+10V
Reference output
ref
2
AI1+
Voltage input frequency reference/DIN4
3
AI1-
I/O Ground
4
AI2+
PID Actual value
5
AI2-
6
+24V
Control voltage output
+
7
GND
I/O ground
8
DIN1
START
9
DIN2
Interlock 1 (par 2.1.15.17 = 10)
10
DIN3
Interlock 2 (par 2.1.15.18 = 13)
11
GND
I/O ground
18
AO1+
Output frequency
mA
Analogue output
19
AO1-
A
RS 485
Serial bus
B
RS 485
Serial bus
21
RO1
22
RO1
23
RO1
Standard I/O expansion
X4
12
+24V
Control voltage output max. 150 mA
13
GND
Ground for controls, e.g. for +24V and DO
14
DIE1
Preset speed 2, par 2.2.1 = 7
15
DIE2
Fault reset, par 2.2.2 = 4
16
DIE3
Disable PID (Freq reference from AI1), par 2.2.3 = 11
X2
25
ROE1/
Autochange 2 (Pump 2 control), par 2.3.2 = 18
COM
26
ROE1/NO
28
TI+
Motor Thermistor input:
29
TI-
Table 1- 19. Example of PFC-control I/O configuration with interlocks and
autochange between 2 pumps
Signal
Autochange 1 (Pump 1 control)
par 2.3.1. = 17
Active = Fault, stop according to defined method
Honeywell

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents