Control I/O - Honeywell NXL Series Applications Manual

Hvac drives
Hide thumbs Also See for NXL Series:
Table of Contents

Advertisement

Page 4 (68)
2.

Control I/O

Reference
potentiometer
2
Control I/O
Terminal
1
+10V
Reference output
ref
2
AI1+
Analogue input, voltage range
0—10V DC.
3
AI1-
I/O Ground
4
AI2+
Analogue input, voltage range
0—10V DC, or current range
5
AI2-
0/4—20mA
6
+24V
Control voltage output
7
GND
I/O ground
8
DIN1
Start forward
9
DIN2
Start reverse (programmable)
10
DIN3
Multi-step speed selection 1
(programmable)
11
GND
I/O ground
18
AO1+
Output frequency
mA
Analogue output
19
AO1-
A
RS 485
Serial bus
B
RS 485
Serial bus
30
+24V
24V aux. input voltage
21
RO1
22
RO1
23
RO1
12
+24V
+24 V DC
13
GND
I/O ground
14
DIE1
Preset speed selection 2
(programmable)
15
DIE2
Fault Reset
(programmable)
16
DIE3
Disable PID (PID control
selection)
(Programmable)
25
ROE1
Expander Relay output 1 (NO)
RUN
26
ROE1
28
TI+
Motor Thermistor input
29
TI-
Table 1- 1. HVAC application default I/O configuration
Terminal
1
+10V
Reference output
ref
2
AI1+
Analogue input, voltage range
or
0—10V DC
DIN 4
3
AI1-
I/O Ground
4
AI2+
Analogue input, voltage range
5
AI2-
0—10V DC or current range
0—20mA
6
+ 24 V
Control voltage output
7
GND
I/O ground
Table 1- 2. The programming of AI1 as DIN4
Signal
Voltage for potentiometer, etc.
Voltage input frequency reference
Can be programmed as DIN4
Ground for reference and controls
Current input frequency reference
(programmable)
Voltage for switches, etc. max 0.1 A
Ground for reference and controls
Contact closed = start forward
Contact closed = start reverse
Contact closed = multi-step speed
Ground for reference and controls
Programmable
Range 0—20 mA/R
Differential receiver/transmitter
Differential receiver/transmitter
Control power supply backup
Relay output 1
Programmable
FAULT
Control voltage output; voltage for
switches etc.
Ground for reference and controls
Contact closed = Preset speed 2
Contact closed = Fault reset
Contact closed = Disable PID
Programmable
Active = Fault, stop according to defined
method
Signal
Voltage for potentiometer, etc.
Voltage input frequency reference (MF2-3)
Voltage/current input frequency reference
(MF4-MF6)
Can be programmed as DIN4
Ground for reference and controls
Voltage
reference
Ground for reference and controls
Honeywell
Description
, max. 500Ω
L
Description
or
current
input
frequency