Output Signals - Honeywell NXL Series Applications Manual

Hvac drives
Hide thumbs Also See for NXL Series:
Table of Contents

Advertisement

Honeywell

4.4 Output Signals

2.3.1
Relay output 1 function
2.3.2
Expander board relay output 1 function
2.3.3
Expander board relay output 2 function
2.3.4
Expander board digital output 1 function
Setting value
0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = Frequency converter overheat
warning
6 = External fault or warning
7 = Reference fault or warning
8 = Warning
9 = Reversed
10 = Preset speed
11 = At speed
12 = Motor regulator activated
13 = Output frequency limit 1
supervision
14 = Control from I/O terminals
15 = Thermistor fault or warning
16 = Actual value supervision active
17 = Autochange 1 control
18 = Autochange 2 control
19 = Autochange 3 control
20 = AI supervision
Table 1- 16. Output signals via RO1 and expander board RO1, RO2 and DO1.
2.3.5
Analogue output function
This parameter selects the desired function for the analogue output signal.
See the table on page 8 for the parameter values.
Description of parameters
Signal content
Out of operation
Relay output RO1 and expander board
programmable relays (RO1, RO2) are activated
when:
The frequency converter is ready to operate
The frequency converter operates (motor is running)
A fault trip has occurred
A fault trip not occurred
The heat-sink temperature exceeds +70°C
Fault or warning depending on par. 2.7.2
Fault or warning depending on par. 2.7.1
- if analogue reference is 4—20 mA and signal is <4mA
Always if a warning exists
The reverse command has been selected
A preset speed has been selected
The output frequency has reached the set reference
Overvoltage or overcurrent regulator was activated
The output frequency goes outside the set
supervision low limit/high limit (see parameters
2.3.12 and 2.3.13 below)
Selected control place (Menu K3; par. 3.1) is "I/O
terminal"
The thermistor input of option board indicates
overtemperature. Fault or warning depending on
parameter 2.7.19.
Parameters 2.7.22 – 2.7.24
Pump 1 control, parameters 2.10.1 – 2.10.7
Pump 2 control, parameters 2.10.1 – 2.10.7
Pump 3 control, parameters 2.10.1 – 2.10.7
The relay energizes according to settings of
parameters 2.3.14 – 2.3.16.
Page 29 (68)