2.3.14
Analogue input supervision
With this parameter you can select the analogue input to be supervised.
0 = Not used
1 = AI1
2 = AI2
2.3.15
Analogue input supervision OFF limit
When the signal of analogue input selected with par. 2.3.14 falls under the limit set with this
parameter, the relay output goes off.
2.3.16
Analogue input supervision ON limit
When the signal of analogue input selected with par. 2.3.14 goes over the limit set with this
parameter, the relay output goes on.
This means that if for example ON limit is 60% and OFF limit is 40%, the relay goes on when
signal goes over 60% and remains on until it falls under 40%.
2.3.17
Relay output 1 ON delay
2.3.18
Relay output 1 OFF delay
With these parameters you can set on- and off-delays to relay output 1 (par 2.3.1).
Signal programmed to
relay output
RO1 output
Figure 1- 9. Relay output 1 on- and off-delays
4
Description of parameters
ON-delay,
par 2.3.17
Honeywell
OFF-delay
par. 2.3.18