4.11.2 Examples
PFC with interlocks and autochange between 3 pumps (the standard I/O expansion board must be
replaced by NXOPTB5 option board)
Situation: 1 controlled drive and 2 auxiliary drives.
Parameter settings: 2.10.1= 2
Interlock feedback signals used, autochange between all drives used.
Parameter settings: 2.10.4=4
DIN4 active (par.2.2.6=0)
The interlock feedback signals come from the digital inputs DIN4 (AI1), DIN2 & DIN3
selected with parameters 2.1.15.17, 2.1.15.18 and 2.2.4.
The control of pump 1 (par.2.3.1=17) is enabled through Interlock 1 (DIN2,
2.1.15.17=10), the control of pump 2 (par.2.3.2=18) through Interlock 2 (DIN3, par.
2.1.15.18=13) and the control of pump 3 (par.2.3.3=19) through Interlock 3 (DIN4)
Reference
potentiometer
2-wire
transmitter
Actual
value
I
(0)4...20 mA
4
Description of parameters
Terminal
1
+10V
Reference output
ref
2
AI1+
Voltage input frequency reference/DIN4
3
AI1-
I/O Ground
4
AI2+
PID Actual value
5
AI2-
+
6
+24V
Control voltage output
7
GND
I/O ground
8
DIN1
START
9
DIN2
Interlock 1 (par 2.1.15.17 = 10)
10
DIN3
Interlock 2 (par 2.1.15.18 = 13)
11
GND
I/O ground
18
AO1+
Output frequency
mA
19
AO1-
Analogue output
A
RS 485
Serial bus
B
RS 485
Serial bus
21
RO1
22
RO1
23
RO1
NXOPTB5
22
RO1/1
Autochange 1 (Pump 1 control), par 2.3.2 = 17
23
RO1/2
25
RO2/1
Autochange 2 (Pump 2 control), par 2.3.3 = 18
26
RO2/2
28
RO3/1
Autochange 3 (Pump 3 control), par 2.3.4 = 19
29
RO3/2
Table 1- 18. Example of PFC-control I/O configuration with interlocks and
autochange between 3 pumps