Input Signals - Honeywell NXL Series Applications Manual

Hvac drives
Hide thumbs Also See for NXL Series:
Table of Contents

Advertisement

Honeywell

4.3 Input Signals

2.2.1
Expander board DIE1 function
This parameter has 12 selections. If the expander board digital input DIN1 need not be used,
set the parameter value to 0.
Selections are as in parameter 2.1.15.18, except:
13 = Interlock 1.
2.2.2
Expander board DIE2 function
The selections are the same as in parameter 2.2.1, except:
13 = Interlock 2
2.2.3
Expander board DIE3 function
The selections are the same as in parameter 2.2.1, except:
13 = Interlock 3
2.2.4
DIN4 Function
If the value of par. 2.2.6 is set to 0, AI1 functions as digital input 4.
The selections are the same as in parameter 2.2.3.
NOTE! If you program the analogue input as DIN4 check that the jumper selections are
correct (see figure below).
Voltage input; 0...10V
Figure 1- 1. Jumper selections of X4 when AI1 functions as DIN4
2.2.5
AI1 signal selection
Connect the AI1 signal to the analogue input of your choice with this parameter.
Description of parameters
MF2
X4:
RS485
programming
Voltage input; 0...10V
MF3
MF4-6
X4:
X8:
Voltage input; 0...10V
Jumperdin4.fh8