• Controller chassis: 4
• Drive chassis:
○ SFF: 16
○ LFF: 16
○ FMD: 8
Required number of PDUs per rack:
• Controller rack
○ Single phase: 4
○ Three phase: 2
• Drive rack:
○ Single phase: 4
○ Three phase: 2

Environmental specifications

The table lists the environmental specifications and requirements for the
storage system.
Table 18 VSP G1000, VSP G1500, and VSP F1500 environmental
Item
Standard Temperature
(ºF / ºC)
high temperature mode
(ºF / ºC)
4
Relative Humidity (%)
Max. Wet Bulb (ºF / ºC)
Temperature deviation
per hour (ºF / ºC)
6
Vibration
Shock
Dust
Altitude
Hitachi Virtual Storage Platform G1000, G1500, and Virtual Storage Platform F1500 Hardware Guide
1
Operating
61 to 90 / 16 to 32
60.8 to 104 / 16 to 40
20 to 80
78.8 / 26
50 / 10
5 to 10Hz: 0.25 mm10 to
300Hz: 0.49m/s2
No impact
Less than 0.15mg per cubic
meter of air
-60 m to 3,000 m
Site preparation
specifications
2
Not Operating
-18 to 122
-10 to 35
8 to 90
80.6 / 27
50 / 10
5 to 10Hz: 2.5mm10 to
70Hz: 4.9m/s270 to 99Hz:
0.05mm99 to 300Hz:
9.8m/s2
2
78.4m/s
(8.0G) 15ms
-
3
Shipping & Storage
-45 to 110 / -25 to 60
5 to 95
84.2 / 29
68 / 20
Sine Vibration: 4.9m/s2,
5min.At the resonant
frequency with the highest
displacement found
7
between 3 to 100Hz
Random Vibration:
0.147m2/s3, 30min, 5 to
7
100Hz
Horizontal: Incline Impact
8
1.22m/s
Vertical: Rotational Edge
10
0.15m
-
-