Modbus Configuration
Modbus Device ID
Read Parameters
Register 0240h
Register 0241h
Register 0242h
Register 0243h
Register 0244h
Register 0245h
Register 0246h
Register 0247h
Register 0240h
Register 0241h
Write Parameters
Register 0250h
Register 0250h
Item
Com Port
Baud Rate
Data Bits
Parity
Stop Bits
Standard
Writing Multiple Registers
Port 2
Selectable: 1-255
Selectable: 9600, 19200, 38400, 57600, or 115200
8
None
1
RS-485
Preset Holding Registers
Pressure SP (Pressure SP /10) (Example 800 = 80 .0 PSI)
Actual Pressure (Pressure PV / 10) (Example 786 = 78 . 6 PSI)
Pump System Mode (0=Lead/Lag; 1=Duplex, Triplex, Quadplex based on model)
Pump System State (0=Maintenance, 1=Commissioning, 2=Manual, 3=Time Based, 4=Day/Time Based)
Pump 1 State OP (0=Off, 1=On)
Pump 2 State OP (0=Off, 1=On)
Pump 3 State OP (0=Off, 1=On)
Pump 4 State OP (0=Off, 1=On)
Read Coils
System Alarm
Pump System State (0=System Off, 1=System On)
Pressure SP (Pressure SP /10) (Example 800 = 80 .0 PSI)
Read Coils
Pump System State (0=System Off, 1=System On)
Options
15