Setup Page 2 - Lag Pump Differential Setting and Pressure Transducer Setups
While on the system screen press
SETUP
SETUP PAGE 2
If a 4-20 ma pressure transducer is used in this system and it has an upper pressure other than
150 psi, input the upper pressure range of the transducer (in psi) in this input box.
Pressure Sensor 20ma
Enter a pressure di erential o of pressure set point for each lag pump in these fields.
Lead/Lag Pump 1 Pressure Di erential from SP
The program will immediately pause pump operation if the transducer reading drops below 3.8 ma.
This prevents run away operation in case of a bad sensor. The user can delay this pause from occurring
by up to 10 seconds by using this field to prevent nuisance shut downs from transient ma readings.
Time Delay Bad Sensor System Shutdown
Go to setup page 3 of setup options
SETUP PAGE 3
Return to setup page 1 of setup options
SETUP PAGE 1
-999.9 PSI
99.9 PSI
99.9 Secs