Pump Capacities; Seawater Cooling System; Central Cooling Water System; Pump Pressures - Man B&W L35MC6-TII Project Manual

Camshaft controlled two-stroke engines
Table of Contents

Advertisement

MAN B&W
The derated cooler capacities may then be found
by means of following equations:
Q
= Q
x (Q
air, M
air, L1
air%
Q
= Q
x (Q
/ 100)
jw, M
jw, L1
jw%
Q
= Q
x (Q
lub, M
lub, L1
lub%
and for a central cooling water system the central
cooler heat dissipation is:
Q
= Q
+ Q
+ Q
cent,M
air,M
jw,M

Pump capacities

The pump capacities given in the 'List of Capaci-
ties' refer to engines rated at nominal MCR (L
For lower rated engines, only a marginal saving in
the pump capacities is obtainable.
To ensure proper lubrication, the lubricating oil
pump must remain unchanged.
Also, the fuel oil circulating and supply pumps
should remain unchanged.
In order to ensure reliable starting, the starting air
compressors and the starting air receivers must
also remain unchanged.
The jacket cooling water pump capacity is rela-
tively low. Practically no saving is possible, and it
is therefore unchanged.

Seawater cooling system

The derated seawater pump capacity is equal to
the sum of the below found derated seawater flow
capacities through the scavenge air and lube oil
coolers, as these are connected in parallel.
The seawater flow capacity for each of the scav-
enge air, lube oil and jacket water coolers can
be reduced proportionally to the reduced heat
dissipations found in Figs. 6.04.01, 6.04.02 and
6.04.03, respectively i.e. as follows:
V
= V
x (Q
sw,air,M
sw,air,L1
V
= V
x Q
sw,lub,M
sw,lub.L1
V
= V
sw,jw,M
sw,lub,M
However, regarding the scavenge air cooler(s),
the engine maker has to approve this reduction in
MAN B&W S46MC-C7/8, S46ME-B8, S42MC7,
S40MC-C9, S40ME-B9, S35MC-C9, S35ME-B9,
S35MC7, L35MC6
/ 100)
/ 100)
lub,M
/ 100)
air%
/ 100)
lub%
order to avoid too low a water velocity in the scav-
enge air cooler pipes.
As the jacket water cooler is connected in series
with the lube oil cooler, the seawater flow capac-
ity for the latter is used also for the jacket water
cooler.

Central cooling water system

If a central cooler is used, the above still applies,
but the central cooling water capacities are used
instead of the above seawater capacities. The
).
seawater flow capacity for the central cooler can
1
be reduced in proportion to the reduction of the
total cooler heat dissipation, i.e. as follows:
V
= V
cw,air,M
V
= V
cw,lub,M
V
= V
cw,jw,M
V
= V
cw,cent,M
V
= V
sw,cent,M

Pump pressures

Irrespective of the capacities selected as per the
above guidelines, the belowmentioned pump
heads at the mentioned maximum working tem-
peratures for each system shall be kept:
Fuel oil supply pump
Fuel oil circulating pump
Lubricating oil pump
Seawater pump
Central cooling water pump
Jacket water pump
Flow velocities
For external pipe connections, we prescribe the
following maximum velocities:
Marine diesel oil ......................................... 1.0 m/s
Heavy fuel oil .............................................. 0.6 m/s
Lubricating oil ............................................. 1.8 m/s
Cooling water ............................................. 3.0 m/s
MAN Diesel
x (Q
/ 100)
cw,air,L1
air%
x (Q
/ 100)
cw,lub,L1
lub%
cw,lub,M
+ V
cw,air,M
cw,lub,M
x Q
/ Q
sw,cent,L1
cent,M
cent,L1
Pump
head bar
4
6
4.0
2.5
2.5
3.0
6.04
Page 2 of 12
Max. working
temp. ºC
100
150
70
50
80
100
198 61 90-6.2