Limits to the length and height difference of refrigerant pipes
The length of the refrigerant pipes between the indoor and outdoor units must be as short as possible and is in any case limited by
compliance with the maximum height difference values between the units.
Diminution of the difference in height between the units (H1,H2) and of the pipe lengths (L) will limit the load losses, consequently
increasing the overall efficiency of the machine.
Comply with the limits given in the following tables.
MOD. OUTDOOR UNIT
MOD. INDOOR UNIT
Connections LIQUID line
Connections GAS line
Length with standard charge
Cooling line maximum length
Maximum diff.in height Outdoor unit low (H1)
Maximum diff.in height Outdoor unit high (H2)
Refrigerant charge
Quantity of additional refrigerant per meter
Contact our technical department for the required modifications if the units must operate beyond the specifications given
above.

Cooling connections indoor unit

Comply with the following indications when connecting the cooling pipes:
• Match the ends of the previously flared pipe with those of the connections on the indoor units or on the cocks of the outdoor units.
• Tighten the union by hand and then torque it with the aid of an adequate wrench (it is advisable to use a fox wedge to prevent
tensions from being created on the pipes).
Cooling connections outdoor unit
Mod. 4 - 6 - 8
14
INSTALLATION
4-6
8
"
"
m
m
20
m
8
m
10
Type
g/m
CONNECTION
fi g. 1
8
10-12-14-16
16
3/8
5/8
10
30
50
15
25
20
30
R410A
54
LIQUID
CONNECTION
12T-14T-16T
16T
50
25
30
GAS