Tank Heater (Electrical Heater For Dhw Tank); Disinfect - Ferroli OMNIA H Series Installation, Maintenance And User Manual

Reversible heat pump for split installation
Table of Contents

Advertisement

Tank heater (electrical heater for DHW tank)

If tank heater (booster heater) is avaliable, Go to FOR SERVICEMAN >DHW MODE SET-
TING>1.2 TANK HEATER and select "Yes", when "OK" pressed, the following page will appear:
Use ◄ ► and ▼▲ to scroll and adjust parameters. Use BACK to exit.
dT5_TBH_OFF is the temperature difference between T5 and T5S that turns the booster heater off. The booster heater will turn
off (T5≥T5S+dT_TBH_OFF) when the heat pump malfunctions.
T4_TBH_ON is the temperature only when the outdoor air temperature is lower than its parameter and the booster heater will be
available.
t_TBH_DELAY is the time that the compressor has run before starting the booster heater (if T5<min (T5S,T5stop)).
The operation of the unit during DHW mode described in the picture below:
In the picture, T5stop is a parameter related to outdoor air
temperature, which cannot be changed in the user interface.
When T5≥T5stop, the heat pump will turn off.
Note:
If the booster heater is unavailable (1.2 TANK HEATER NON
is selected), the dT5_ON cannot be adjusted and is fi xed at 2.
NOTE
The booster heater of DHW tank (THB) and backup heater of the system (electrical booster IBH) can't operate simulta-
neously, if the booster heater has been on, the backup heater will be off and viceversa.

Disinfect

To enable disinfect function,Go to MENU> FOR SERVICEMAN>DHW MODE
SETTING>1.3 DISINFECT and select "YES", when "OK" pressed, the following
page will appear.
T5S_DI is the target temperature of water in the domestic hot water tank
in the DISINFECT function.
t_DI_HIGHTEMP is the time that the hot water will last.
t_DI_MAX is the time that disinfection will last. The change of domestic
water temperature is described in the picture below:
Be aware that the domestic hot water temperature at the hot water
tap will be equal to the value selected in FOR SERVICEMAN
"T5S_DI" after a disinfection operation.
SETUP OF THE SYSTEM
min(T5S,T5stop)-dT5_on
T5
T5S+dT5_TBH_OFF
T5S
T5stop
COMP.
OFF
TBH
t_TBH_delay
T5
T5S_DI
T5S
1.2 TANK HEATER
dT5 TBH OFF
T4_TBH_ON
20°C
_TBH_DELAY
90 MIN
SCROLL
ON
OFF
ON
OFF
Time
1.3 DISINFECT
T5S_DI
65 °C
t_DI_HIGHTMEP.
30 MIN
t_DI_MAX
120 MIN
SCROLL
t_DI_HIGHTEMP
t_DI_MAX
5 °C
t
31