If ►is pressed, the main page will display the room temperature:
If you set WATER FLOW TEMP. to NON, and set ROOM TEMP. to YES, then the room
temperature will be displayed on the home page, and the room temperature will work as
the target temperature. The target outlet water temperature can be calculated from the
climate related curves.

Room thermostat (ON/OFF - HEAT/COOL by digital input)

NOTE
The ROOM THERMOSTAT submenu allows you to set the unit operation based on the status of digital inputs on the
unit's control board.
To set the ROOM THERMOSTAT, go to MENU> FOR SERVICEMAN> ROOM THERMO-
STAT. Press OK. The following page is displayed:
If you want to connect a room thermostat (or a remote switch) for the activation and turning off the unit, ROOM THERMOSTAT
must be set to YES and the MODE SETTING must be set to NON. With this setting, the unit will operate in the mode set as a user
interface only when the thermostat closes the contact.
If you want to connect instead a double contact thermostat (or 2 remote switches) to determine the activation of the unit in HEAT
or COOL, ROOM THERMOSTAT must be set to YES and the MODE SETTING must be set to YES. With this setting, the unit will
operate in the mode required by the thermostat (or by one of two remote switches) and therefore will not be possible to activate the
unit nor to change the operation mode through the user interface.
If you set the unit to be activated via digital inputs the timer function and weekly scedule are not available;
The temperature adjustment can be performed from the user interface.
NOTE
"DUAL ROOM THERMOSTAT" must not be used: set to NON.
NOTE: The setting in the user interface MUST match the thermostat wiring (or remote switches). For more information also see
"ELECTRICAL CONNECTIONS".
36
SETUP OF THE SYSTEM
21: 55 08 - 08 - 2015 SAT.
ROOM
ON
c
24
SET
21: 55 08 - 08 - 2015 SAT.
ON
ROOM
DHW
ON
c
c
24
55
SET
TANK
6 ROOM THERMOSTAT
ROOM THERMOSTAT
YES
NON
YES
NON
MODE SETTING
YES
NON
DUAL ROOM
THERMOSTAT
SCROLL