Water Connections; Connection Diagram; Position Of Connections; Hydraulic Data - Ferroli RCI 35-40 Installation, Maintenance And User Manual

A class energy efficiency aircooled liquid chillers and heat pumps with axial fans, inverter scroll compressor and ec inverter
Table of Contents

Advertisement

4. Water
connections
4.1

Connection diagram

4.2

Position of connections

4.3

Hydraulic data

4.4
Connection to the system
4.5
System fill-up
4.1 Connection diagram
1
Unit
ANT
Anti-vibration joint (recommended)
CV
Check valve
FL
Flow switch (mandatory)
FTR
Mesh filter (mandatory)
MN
Water gauge
MP
Circulating pump
RI
Shut-off ball valve
RIC
Automatic water filling valve
SFA
Automatic air vent (mandatory)
ST
Inertial tank
VE
Expansion vessel
VSI
Safety valve (mandatory)
Some of the components in the diagram may already be included in the unit with the
hydronic kit. Those not included must be provided by the installer.
Connection pipes must have a suitable diameter and be supported so as not to impose
their weight on the unit.
4.2 Position of connections
The position of the water connections and the inlet and outlet direction is indicated by the labels
on the connections.
4.3 Hydraulic data
4.3.1 Water volume
The machine electronic control, to protect the electrical motor, limits hourly start up of the
compressor.
This operation creates oscillations of the water temperature in the draw-off point, affecting plant
efficiency.
For a proper operation it is necessary the water content complies with the following table:
Evaporator water flow
Pmin
Pmax
V
Pmin
Evaporator minimum flow
14
Model
91
101 131 151
l/s
0.95 0.85 1.01 1.14
l/s
1.85 2.26 2.71 3.05
L
70
85
105 120
Pmax
Evaporator maximum flow
V
Water volume
If the water volume in the circuit (V) does not reach what is indicated, installing a new inertial
storage tanks shall be required.
4.3.2 Water features
Water features are important for the proper operation of the machine and for its lifetime.
Extreme water hardness leads to the formation of limestone in exchangers reducing their
performance.
The table shows some water parameters to be observed for proper operation of the machine.
Content
pH
Alkalinity
HCO3
Sulphate
SO42-
Alkalinity/Sulphate
HCO3-/SO42-
Electrical conductivity
μS/cm
Ammonium
NH4
Free chlorine
Cl2
Hydrogen Sulphide
H2S
Free Carbon Dioxide
CO2
Nitrate
NO3
Iron
Fe
Aluminium
AL
Manganese
MN
1 - Good corrosion resistance.
2 - If different factors of this type are present, corrosion can occur.
3 - Use not recommended.
4.3.3 Protection against freezing
If you do not wish to drain the system during periods where the machine is not used, the water
may freeze, or if the system must operate with temperatures less than 5°C, ethylene glycol must
be mixed with the water.
Material
Concentration mg/l or ppm
AISI 316L Copper
<6
2
6-7.5
2
7.5-9
1
>9
1
- <70
1
70-300
1
>300
1
<70
1
70-300
1
>300
1
>1
1
<1
1
<10
1
10-500
1
>500
1
<2
1
2-20
1
>20
1
<1
1
1-5
3
>5
3
<0.05
1
>0.05
1
<5
1
5-20
1
>20
1
<100
1
>100
1
<0.2
1
>0.2
1
<0.2
1
>0.2
1
<0.1
1
>0.1
1
2
2
1
2
2
1
2
1
3
3
1
3
2
1
2
1
2
3
1
1
3
1
3
1
2
3
1
2
1
2
1
2
1
2