4.6 Register Allocation for Function 03 / 06 / 16 – Read / Write Holding Registers
All registers use 16 bit data words.
The Channel Type field identifies the channel as Input or Output. The decimal value 105 (= ASCII 'i') is used for Inputs.
Function 16 can be used to write to the 40n01 to 40n04 and 41n01 to 41n05 (n = 0 to 9) ranges of registers only.
Caution: When using Function 6 or Function 16, ensure that the registers related to the command are completely filled
before setting the Block Active flag, otherwise an unintended command may be performed.
4.6.1

Query Poll Registers

Query Poll
Block Active
Block
1
2
3
4
5
6
7
8
9
10
Allowed values for the Result register 40n05 (n = 0 to 9):
MAN0995_Iss 1_01/16
Pt. No. 3011M5027_1
M
ODBUS
Channel Type
40001
40002
40101
40102
40201
40202
40301
40302
40401
40402
40501
40502
40601
40602
40701
40702
40801
40802
40901
40902
Table 8.
Value
0
Success
1
Command not permitted
2
Inter process communication failure
67
Failure
Table 9.
Query Poll Register Values
C
ONFIGURATION
Channel ID
Query Type
40003
40004
40103
40104
40203
40204
40303
40304
40403
40404
40503
40504
40603
40604
40703
40704
40803
40804
40903
40904
Query Poll Register
Meaning
13
Result
Result String
40005
40006 to 40036
40105
40106 to 40136
40205
40206 to 40236
40305
40306 to 40336
40405
40406 to 40436
40505
40506 to 40536
40605
40606 to 40636
40705
40706 to 40736
40805
40806 to 40836
40905
40906 to 40936
Touchpoint Plus