Technical Data - Honeywell AQS51-KAM Product Data

Combined co2-/temperature duct sensor/controller
Table of Contents

Advertisement

AQS51/61-KAM COMBINED CO
MODELS
Type
CO
and Temperature Duct
2
Sensor without LCD display
CO
and Temperature Duct
2
Sensor with 4-digit LCD display

TECHNICAL DATA

General
CO
- Measurement
2
Temperature
Measurement
P+ + + + I control
EN0B-1023 GE02R0700
-/TEMPERATURE DUCT SENSOR/CONTROLLER
2
Order Number
AQS51-KAM
AQS61-KAM
Power supply
Power consumption
Sensor life expectancy
Maintenance interval
Self diagnostics
Status LED indication
Power-up time
Ambient operating limits
- Temperature
- Humidity
Operating principle
Gas sampling mode
Response time
Measurement range
Converting range
Accuracy
Pressure dependence
Annual zero drift
Operating principle
Measurement range
Converting range
Accuracy
Settings and configuration with
Service Software AQS-USP22
- Throttling range CO
2
- Throttling range temperature
- Reset time adjustment ranges
ACCESSORIES
Description
Service Software; 3.5" Diskette
(for changing the sensing range, the
parametrization and the post calibration)
Testset
(consists of a portable gas generator for
zero-position calibration, pump, packing,
3m tube, battery and transformer)
RS Cable with built-in electronics and
adapters
24Vac ± 20%; 50/60Hz or 24Vdc ± 20%
2W
>15 years
5 years
Complete power/sensor/analog outputs internal test
Yellow = Maintenance required; Red = Relay activated
≤1 min
0...50°C
0...95%rh (non condensing)
Non-dispersive infrared (NDIR)
Diffusion and ∅3 mm gas inlet push-on barb
2 min (diffusion) or 10 sec (0.2 ltr/min gas flow)
0...3000 ppm
0...2000 ppm = 0...10 Vdc (factory setting)
or 2...10 Vdc / 0...20 mA / 4...20 mA
±1% of measurement range, ±5% of reading
+1.58% of reading per kPa deviation from normal pressure
100 kPa
< ±1% of measurement range
Thermistor
−10...60°C
0...50 °C = 0...10 Vdc (factory setting) or 2...10 Vdc / 0...20
mA / 4...20 mA
±0.2 K
100...800 ppm
1...10 K
2...500 sec (factory setting: 300 sec)
2
Order Number
AQS-USP22
AQS-F0005
AQS3/4 or
AQS31/41

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aqs61-kam

Table of Contents