AQS51/61-KAM COMBINED CO
Pin
Jumper
1
2
AN1
3
4
5
AN2
6
7-8
OUT
9-10
WIRING
Connection Terminal
G+
G0
OUT1
OUT2
M
NC
CM
NO
NOTE1: The ground terminal is used as negative power
supply DC input or AC phase ground G0 (halfwave
rectifier). The signal ground M, protected by a PTC
resistor, is the same as power ground G0
(permitting a "3-wire" configuration). A single
transformer may be used for the entire system.
Situations can occur where different transformers
must be used.
NOTE2: AQS51/61 can supply both a voltage or a current
output for OUT1/OUT2. To change between
voltage and current output mode the hardware
jumpers have to be set in accordance. There is
one jumper for AN1 and one for AN2, so that one
output can be a voltage output and the other a
current output. Both voltage output and current
output can be 0...100% (0...10 Vdc or 0...20 mA)
or 20...100% (2...10 Vdc or 4...20 mA) The same
percentage are used for both outputs, see Table 1.
Wiring should be done only according to the actual job wiring
diagrams or above wiring list. All wiring must conform to
applicable codes, ordinances and regulations.
Electric discharge may damage the sensor electronics.
Therefore handle the unit carefully and avoid electrostatic
discharge.
Do not connect the power supply unless all other connections
and settings are correctly done.
The AQS51/61 signal ground (M) is not galvanically
separated from the power supply. If the analog output signals
are connected to controllers or DDC system, the same
EN0B-1023 GE02R0500
-/TEMPERATURE DUCT SENSOR/CONTROLLER
2
Marked
Current
Current/Voltage
Voltage
Current
Current/Voltage
Voltage
20 - 100%
0 - 100%
Table 1 Jumper selections
Function
Power+
Power ground (-)
Analogue output 1 (+)
Analogue output 2 (+)
Signal ground (-)
Normally closed
Common relay terminal
Normally open
Table 2 Electrical terminal connections
Pin 1 and 2 provides 0(4)...20mA for OUT1
Pin 2 and 3 provides 0(2)...10Vdc for OUT1
Pin 4 and 5 provides 0(4)...20mA for OUT2
Pin 5 and 6 provides 0(2)...10Vdc for OUT2
Pin 7 and 8 provides 2...10Vdc or 4...20mA
Pin 9 and 10 provides 0...10Vdc or 0...20mA
Electrical Data
24Vac/dc+
24Vac/dc-
0...10Vdc, 0...20mA,
2...10Vdc, 4...20mA
0...10Vdc, 0...20mA,
2...10Vdc, 4...20mA
Potential free contact
relay
1mA/5V up to
1A/50Vac/24Vdc
ground potential has to be used or install separate
transformers for sensor and controller/DDC system.
6
Function
Remarks
Internal rectifying diode
(see Note 1!)
According to OUT, AN1
jumper positions
According to OUT, AN2
jumper positions
Protected by PTC resistor
Triggered by register
OUT3