Digilite® Technical Specification - Protec Digilite Installation Manual

Emergency lighting control panel
Table of Contents

Advertisement

8.0
Digilite® Technical Specification
Power Supply Mains
Integral Charger
Auxiliary 24V output
Maximum Battery Size
Mains Fuse
Battery Fuse
Working Voltage
Current Consumption
Temperature Range
Humidity Limit
Environment
Mounting
N93-561-85 Issue 0
230V AC. Nominal (+/-10%)
1A switch mode, temperature compensated, 250mA battery charge current.
Batteries monitored for disconnection, failure and deep discharge
24V DC, 100mA max, monitored for fuse failure. (fuse self resetting)
2 x 12V 3.3Ah
1A HRC ceramic 20mm
1.6A F 20mm
20V to 30V DC
15mA (24V DC. Supply, not in alarm, mains failed, buzzer slow beeping,
General and PSU fault light illuminated) + loop load
0 to 40 degrees C
85% Non-Condensing
Meets IP30 if mounted in a dry position that does not exceed the temperature
and humidity limits given
3 or 4 points surface mount
13
© Copyright Protec Fire Detection plc 2009