6. Specifications
NOTE: Product specifications are subject to change without notice.
Input
MODEL/CAPACITY
Acceptable Voltage
Range
Frequency Range
Output
MODEL/CAPACITY
Voltage Regulation
(Battery Mode)
Frequency Range
(Battery Mode)
Current Crest Ratio
Harmonic Distortion
Transfer Time
Waveform
(Battery Mode)
Efficiency
MODEL/CAPACITY
AC Mode
Buck & Boost Mode
Battery Mode
Battery
MODEL/CAPACITY
Battery Type & Number
Charging Voltage
Recharge Time
Charging Current
Protection
MODEL/CAPACITY
Full Protection
1100VA
990W
1100VA
990W
110/115/120/127 Vac ±1.5% (before battery alarm)
2% max @ 100% linear load, 5% max @ 100% non-linear load
1100VA
990W
88%
1100VA
990W
12 V/9 Ahx2
27.4 VDC ± 1%
1100VA
990W
Overload, short, discharge, and overcharge protection
1500VA
1350W
81-145 Vac
60/50 Hz (auto sensing)
1500VA
1350W
50 Hz or 60 Hz ± 1 Hz
3:1
(before low battery alarm)
Typical 2-6 ms, 10ms max.
Pure Sine Wave
1500VA
1350W
95%
93%
90%
1500VA
1350W
12 V/7 Ahx4
12 V/9 Ahx4
54.8 VDC ± 1%
4 hours recover to 90% capacity
1.5A
1500VA
1350W
28
2000VA
3000VA
1800W
2700W
2000VA
3000VA
1800W
2700W
2000VA
3000VA
1800W
2700W
2000VA
3000VA
1800W
2700W
12 V/9 Ahx6
82.1 VDC ± 1%
2000VA
3000VA
1800W
2700W
90%