Touch screen flush-mount room thermostats with knx communications for 2-pipe, 2-pipe with electrical heater, and 4-pipe fan coil units, for universal applications, for use with compressors in dx type equipment
Hide thumbs Also See for RDF800KN:
Table of Contents

Advertisement

Reset
Applications
Connect tool
Note:
12 / 20
Siemens
Building Technologies
LCD display
Parameter
Functionality of X1
Functionality of X2
Operating action
of X1
Operating action
of X2
If more details are required about parameters, refer to basic documentation P3174.
To re-load factory settings for all parameters, set parameter P71 to ON. Restart the
thermostat after reset, all LCD segments flash, indicating that the reset is correct.
3 seconds later, the thermostat is ready for commissioning by qualified HVAC staff.
The room thermostats are delivered with a fixed set of applications. Select and
activate the relevant application during commissioning using one of the following
tools:
Local DIP switch and HMI
Synco ACS
ETS4
Connect the Synco ACS or ETS4 tools to the KNX bus cable at any point for
commissioning:
KNX
L
X1
M X2
CE+ CE-
N
Q1 Q2 Q3
Y1
RDF800KN..
ACS and ETS4 require an interface:
RS232 KNX interface (such as Siemens N148 / UP146 / UP152)
OCI700 USB - KNX interface
An external KNX bus power supply is required if an RDF800KN... is connected
directly to a tool (ACS or ETS4) via KNX interface.
RDF800KN...
Touch Screen Flush-mount Room Thermostats with KNX Communications
Range
0: --- No function
1: Ext / Return Temp (AI)
2: H/C changeover (AI/DI)
3: Window open detect (DI)
4: Dew point sensor (DI)
5: Enable electr. Heater (DI)
6: Fault input (DI)
7: Monitor input (Digital)
8: Monitor input (Temp)
10: Presence detection (DI)
Normal Open (NO)
Normal Close (NC)
-
End of wizard
Y2
RS232
ETS4
Factory setting
3
1
Normal Open
(NO)
Siemens
N148 /
UP146 /
UP152
ETS4 / ACS
CB1N3174en
2014-09-10
-
Siemens
OCI700
or
OCI702...