Inputting Device Information; Tag, Date, Descriptor And Message - Emerson Rosemount 644 Reference Manual

Temperature transmitter with hart protocol
Hide thumbs Also See for Rosemount 644:
Table of Contents

Advertisement

Section 2: Configuration
April 2015
Configuring LCD display with AMS Device Manager
1.
2.
3.
4.
5.
Configuring LCD display with LOI
Reference the figure below to find the LCD display value configuration path on the LOI.
Figure 2-17. Configuring the LCD Display with the LOI
VIEW CONFIG
SENSOR CONFIG
UNITS
RERANGE
LOOP TEST
DISPLAY
DISPLAY
EXTENDED MENU
EXIT MENU
* Available only if option code (S) or (D) is ordered.
2.9

Inputting device information

Access the transmitter information variables on-line using the Field Communicator or other
suitable communications device. The following is a list of transmitter information variables,
including device identifiers, factory-set configuration variables, and other information.
2.9.1

Tag, date, descriptor and message

The Tag, Date, Descriptor and Message are parameters that provide transmitter identification in
large installations. See below for a description and a process to enter these pieces of
configurable device information.
The Tag variable is the easiest way to identify and distinguish between different transmitters in
multi-transmitter environments. It is used to label transmitters electronically according to the
requirements of the application. The defined Tag is automatically displayed when a HART-based
communicator establishes contact with the transmitter at power-up. The Tag is up to 8
characters and the Long Tag (a parameter introduced with the HART 6 and 7 protocol) was
32
Right click on the device and select Configure.
In the left navigation pane select Manual Setup.
On the Display Tab there will be a group box with all available variables that can be
displayed.
Check and un-check the desired display variables, with a checked box indicating that
the variable will be displayed.
Select "Apply" when complete.
SENSOR 1
SENSOR 2*
ANALOG
PV
AVG*
1
GOOD*
ST
DIFF*
% RANGE
TERM
MNMAX1*
MNMAX2*
MNMAX3*
MNMAX4*
BACK TO MENU
EXIT MENU