Siemens 7SV512 Instruction Manual page 59

Numerical circuit breaker failure protection v1.0
Table of Contents

Advertisement

7SV512
V1
Note as to Table 5.3: Annunciations with the function numbers below 100 are identical with those for binary
inputs. They represent the direct confirmation of the binary input and are available as long as the correspond-
ing binary input is energized. These direct confirmation functions are indicated by a leading ">" sign.
Further information about annunciations see Section 6.4.
FNo
Abbreviation
1
not allocated
5
>Time Synchro
6
>LED-reset
7
>Start FltRec
16
>CB Aux. L1
17
>CB Aux. L2
18
>CB Aux. L3
19
>CB Aux. 3p C
20
>CB Aux. 1p C
21
>Annunc. 1
22
>Annunc. 2
23
>Annunc. 3
24
>Annunc. 4
31
>B/F on
32
>B/F off
33
>Pole Dis. on
34
>Pole Dis.off
35
>Flt.Rec. on
36
>Flt.Rec. off
59
>ParamSelec.1
60
>ParamSelec.2
70
>Start
71
>Start N
72
>Trip
73
>Trip 3pole
74
>Trip L1
75
>Trip L2
76
>Trip L3
77
>B/F block
78
>CB defect
101
Dev.Operative
107
Flt.Rec.Trans
108
Fault.Rec.off
110
Param.Running
116
Param. Set A
117
Param. Set B
118
Param. Set C
119
Param. Set D
121
Failure 18V
122
Failure 15V
123
Failure 5V
124
Failure 0V
125
Failure RKA
151
Failure
I
154
Failure Isymm
469
Device FltDet
470
Device Trip
471
BFP off
472
BFP-Pickup
473
BFP-Start
Table 5.3
Marshalling possibilities for signal relays and LEDs (Continued next page)
C53000---G1176---C91
Binary output is not allocated to any output function
Synchronize internal real time clock
Reset LED indicators
Start fault recording from external command via binary input
Circuit breaker auxiliary contact L1 (L1 is closed)
Circuit breaker auxiliary contact L2 (L2 is closed)
Circuit breaker auxiliary contact L3 (L3 is closed)
Circuit breaker auxiliary contact all poles closed (series connection)
Circuit breaker auxiliary contact any pole closed (parallel connection)
User definable annunciation 1
User definable annunciation 2
User definable annunciation 3
User definable annunciation 4
Switch on breaker failure protection
Switch off breaker failure protection
Switch on pole discrepancy supervision
Switch off pole discrepancy supervision
Switch on fault recording function
Switch off fault recording function
Parameter set selection 1 (in connection with 060)
Parameter set selection 2 (in connection with 059)
General fault detection signal from feeder protection
Earth fault detection signal from feeder protection
General trip signal from feeder protection
Trip signal three-pole from feeder protection
Trip signal L1 from feeder protection
Trip signal L2 from feeder protection
Trip signal L3 from feeder protection
Block breaker failure protection
Circuit breaker defective (from circuit breaker monitor)
Relay operative
Fault record data are available or being transmitted
Fault recording switched off
Parameters are being set
Parameter Set A is activated
Parameter Set B is activated
Parameter Set C is activated
Parameter Set D is activated
Failure in 18 V internal dc supply
Failure in 15 V internal dc supply
Failure in 5 V internal dc supply
Failure in 0 V A/D converter
Failure in base input/output module
Failure supervision I (measured currents)
Failure supervision symmetry I
General fault detection signal
General trip signal
Breaker failure protection switched off
Breaker failure protection initiated (signal from feeder protection)
Breaker failure protection started
Description
Installation instructions
59