Programming The Scope Of Functions - Siemens 7SV512 Instruction Manual

Numerical circuit breaker failure protection v1.0
Table of Contents

Advertisement

7SV512
V1
5.4.2
Programming the scope of functions --- address block 78
The available functions can be programmed as ex-
isting or not existing. For some functions it may also
be possible to select between multiple alternatives.
Functions which are configured as NON EXIST will
not be processed in 7SV512: There will be no annun-
ciations and the associated setting parameters
(functions, limit values) will not be requested during
setting (Section 6.3). In contrast, switch-off of a
7 8 0 0
S C O P E
F U N C T I O N S
7 8 2 8
F A U L T
E X I S T
N O N
E X I S T
7 8 3 8
P O L E
N O N - E X I S T
E X I S T
The rated system frequency must comply with the setting under address 7899. If the system frequency is not
50 Hz, address 7899 must be changed.
7 8 9 9
F R E Q U E N C Y
f N
5 0
H z
f N
6 0
H z
52
O F
Beginning of the block "scope of functions"
R E C R D
D I S C R P
Rated system frequency 50 Hz or 60 Hz
function means that the function will be processed,
that indication will appear (e.g. "... switched off") but
that the function will have no effect on the result of
the protective process (e.g. no command).
The following boxes show the possibilities for the
maximum scope of the device. In an actual case,
functions which are not available will not appear in
the display.
7 8 6 9
L S A
N O N - E X I S T
E X I S T
7 8 8 5
P A R A M .
N O N - E X I S T
E X I S T
Installation instructions
C / O
C53000---G1176---C91