Checking The Lsa Data Transmission Link - Siemens 7SV512 Instruction Manual

Numerical circuit breaker failure protection v1.0
Table of Contents

Advertisement

7SV512
V1
5.2.3

Checking the LSA data transmission link

For models with an interface for a central data pro-
cessing station (e.g. LSA) these connections must
also be checked. It is important to visually check the
allocation of the transmitter and receiver channels.
Since each connection is used for one transmission
direction, the transmit connection of the relay must
be connected to the receive connection of the cen-
tral unit and vice versa.
Transmission via optical fibre is particularly insensi-
tive against disturbances and automatically pro-
vides galvanic isolation. Transmit and receive con-
nectors are designated with the symbols
transmit output and
Figure 5.3
Position of the jumper X91 on the CPU board (EPS)
44
for
for receive input.
R124
X103
X91
+
T4
The normal signal position for the data transmission
is factory preset as "light off". This can be changed
by means of a jumper plug X91 which is accessible
when the plug-in module is removed from the case.
The jumper is situated in the rear area of the CPU
board (EPS) between the connector modules (Fig-
ure 5.3).
Jumper
Position
X91
90 --- 91
X91
91 --- 92
V 40
V39
D11
X104
R94
T3
Jumper X90---X91 at delivery
Installation instructions
Normal signal position
"Light off"
"Light on"
C53000---G1176---C91