ABB REF615 ANSI 5.0 FP1 Product Manual page 54

Feeder protection and control
Table of Contents

Advertisement

54
R E F 6 1 5 A N S I 5 . 0 F P 1 F E E D E R P R OT E C T I O N A N D C O N T R O L
Table 78. Fault locator (SCEFRFLO) main settings
Parameter
Z Max phase load
Ph leakage Ris
Ph capacitive React
R1 line section A
X1 line section A
R0 line section A
X0 line section A
Line Len section A
Table 79. High-impedance fault detection (PHIZ) main settings
Parameter
Security Level
System type
Table 80. Reverse power/directional overpower protection (DOPPDPR)
Characteristic
Operation accuracy
1)
Start time
2), 3)
Reset time
Reset ratio
Operate time accuracy
Suppression of harmonics
1) Measurement mode = "Pos Seq" (default)
2) U = U
, f
= 50 Hz, results based on statistical distribution of 1000 measurements
n
n
3) Includes the delay of the signal output contact
Table 81. Reverse power/directional overpower protection (DOPPDPR) main settings
Parameter
Start value
Operate delay time
Directional mode
Power angle
Table 82. Underpower protection (DUPPDPR)
Characteristic
Operation accuracy
1)
Start time
2), 3)
Reset time
Reset ratio
Operate time accuracy
Suppression of harmonics
1) Measurement mode = "Pos Seq" (default)
2) V = V
, f
= 50 Hz, results based on statistical distribution of 1000 measurements
n
n
3) Includes the delay of the signal output contact
Function
SCEFRFLO
SCEFRFLO
SCEFRFLO
SCEFRFLO
SCEFRFLO
SCEFRFLO
SCEFRFLO
SCEFRFLO
Function
PHIZ
PHIZ
Function
DOPPDPR
DOPPDPR
DOPPDPR
DOPPDPR
Value (range)
1.0...10000.00 Ω
20...1000000 Ω
10...1000000 Ω
0.000...1000.000 Ω/pu
0.000...1000.000 Ω/pu
0.000...1000.000 Ω/pu
0.000...1000.000 Ω/pu
0.000...1000.000 pu
Value (range)
1...10
1 = Grounded
2 = Ungrounded
Value
Depending on the frequency of the measured current and voltage:
f = f
±2 Hz
n
Power measurement accuracy ±3% of the set value or ±0.002 × Sn
Phase angle: ±2°
Typically 45 ms
Typically 30 ms
Typically 0.94
±1.0% of the set value of ±20 ms
-50 dB at f = n × f
, where n = 2, 3, 4, 5,...
n
Value (range)
0.01...2.00 × S
n
40...300000 ms
2 = Forward
3 = Reverse
-90...90°
Value
Depending on the frequency of the measured current and voltage:
f
±2 Hz
n
Power measurement accuracy ±3% of the set value or ±0.002 × Sn
Phase angle: ±2°
Typically 45 ms
Typically 30 ms
Typically 1.04
±1.0% of the set value of ±20 ms
-50 dB at f = n × f
, where n = 2, 3, 4, 5,...
n
Step
0.1
1
1
0.001
0.001
0.001
0.001
0.001
Step
1
-
Step
0.01
10
-
1